Revised Ordinances of Honolulu

(Link to original Word Processing Version)


     Article 8. Building Envelope

Sections:
32-8.1    Scope.
32-8.2    General.
32-8.3    Calculation procedures and basic requirements.
32-8.4    Prescriptive criteria.
32-8.5    Systems performance criteria.
(32-8.6    Notice to owner of cost of insulation or radiant barrier. Repealed by Ord. 01-46.)
32-8.6    Reserved.

Sec. 32-8.1    Scope.
(a)    The requirements of this article apply to all buildings or portions of buildings which provide shelter or facilities for human occupancy. The requirements apply to new buildings and to additions which increase the floor space of existing buildings.
(b)    Exception. Buildings or portions of buildings with open walls or other permanently open elements of the building envelope.
(Added by Ord. 94-75)

Sec. 32-8.2    General.
(a)    Compliance. The building envelope is in compliance with the requirements of this article when all of the following conditions are met:
(1)    The required calculation procedures of Section 32-8.3 are used, and the basic requirements (air leakage and comfort ventilation) of Section 32-8.3 are satisfied;
(2)    Opaque roof surfaces are in compliance with the prescriptive criteria, Section 32-8.4;
(3)    Opaque wall surfaces are in compliance with the prescriptive criteria, Section 32-8.4 or, alternatively, the entire wall (including glazing) is in compliance with the system performance criteria, Section 32-8.5;
(4)    Vertical glazing is in compliance with the prescriptive criteria, Section 32-8.4, or alternatively, the entire wall (including opaque) is in compliance with the system performance criteria, Section 32-8.5; and
(5)    Horizontal glazing is in compliance with the prescriptive criteria, Section 32-8.4.
(b)    Climate. If local building site climate data is not available, climate data from a nearby location with a similar climate may be used.
(Added by Ord. 94-75)

Sec. 32-8.3    Calculation procedures and basic requirements.
(a)    Overall Thermal Transmittance (Uo). The overall thermal transmittance of the opaque portion of walls and roofs shall be calculated in accordance with Equation 8-1.


Equation 8-1


Σ UiAi        U1A1 + U2A2 +...+ UnAn
Uo =    ______    =    _________________________
Ao              Ao

where:

Uo =        The area-weighted average thermal transmittance of the opaque wall or roof [Btu/h-ft2-ºF].

Ao =        The gross area of the opaque elements of the wall or roof [ft2]. (See subsection (c).)

Ui =        The thermal transmittance of each individual element of the envelope assembly with a unique U-value [Btu/h-ft2-ºF] (see subsection (b)). Equal to 1/Ri (where Ri is the total resistance to heat flow of an individual path through an envelope assembly).

Ai =        The area of the element of the envelope assembly which has U-value, Ui [ft2].

(b)    Thermal Transmittance (Ui). The thermal transmittance of each individual element of the envelope assembly shall be determined with due consideration of surface conductances and all major series and parallel heat flow paths.
(c)    Gross Area of Opaque Envelope Components.
(1)    The gross area of an opaque roof surface consists of the total surface of the roof assembly exposed to outside air or unconditioned spaces. The opaque roof assembly shall exclude skylight surfaces, service openings, and overhangs.
(2)    The gross area of opaque exterior wall surfaces is measured on the exterior and includes between-floor spandrels, peripheral edges of flooring and door areas. The opaque wall surface excludes vents, grilles, pipes and windows.
(d)    Relative Solar Heat Gain (RSHG).
    (1)    The vertical fenestration solar heat gain limits are expressed in terms of maximum relative solar heat gain (RSHG). Relative solar heat gain shall be calculated as determined in this section. When a fenestration system includes an overhang or sidefins, then the RSHG shall be calculated with either Equation 8-2 for an overhang or Equation 8-3 for sidefins. For a single window, either the overhang multiplier, OHM, or the sidefin multiplier, SFM, but not both, may be used for shading credit.
or


Equation 8-2



RSHGi = SCglz,i x
OLE Object Here
x SCext,i x OHMi



Equation 8-3



RSHGi = SCglz,i x
OLE Object Here
x SCext,i x SFMi


where:

RSHGi =    Relative solar heat gain.

SCglz,i =    Shading coefficient of the glass alone taken from the manufacturer's literature.

ISprop =    Interior and/or integral shade shading coefficient adjustment, based on the proposed type of shade and the type of glass. Equal to the ratio of the shading coefficient with shades to the shading coefficient of the glazing alone (SCglz). As a default, ISprop. may be assumed to equal ISdef. (then ISprop./ISdef. = 1.0). (Unitless.)

ISdef=Default shading coefficient adjustment. For a medium-colored venetian blind with the proposed glazing. Equal to the ratio of the shading coefficient of the fenestration with a medium- colored venetian blind to the shading coefficient of the glazing alone. (Unitless.)

SCext =    Shading coefficient of exterior shade screens or louvers. Default is 1.0. (Unitless.)

OHMi =    Overhang Multiplier. Calculated as a function of Overhang Projection Factor, OPF. From Equation 8-4 or Table 8-3.

SFMi =     Sidefin Multiplier. Calculated as a function of the Sidefin Projection Factor, SPF. From Equation 8-5 or Table 8-4.

The overhang and sidefin multipliers are calculated with the following equations.


Equation 8-4

OHMi = 1 + ai x OPFi + bi x OPFi2


where:

OHM =    Overhang Multiplier.

OPF =    Overhang Projection Factor. The maximum value allowed for credit is 1.5. From Equation 8-6.

a, b =     Coefficients which depend on orientation. From Table 8-1.



Equation 8-5

SFMi = 1 + ci x SPFi + di x SPFi2



where:

SFM =    Sidefin Multiplier.

SPF =    Sidefin Projection Factor. The maximum value allowed for credit is 1.5. From Equation 8-7.

c, d =     Coefficients which depend on orientation. From Table 8-2.

Table 8-1 -- Overhang Multiplier Coefficients

Orientation    a    b

North    -0.440    0.123
East, West and South    -0.840    0.245




Table 8-2 -- Sidefin Multiplier Coefficients

Orientation    c    d

North    -0.81    0.27
East    -0.51    0.13
South    -0.65    0.16
West    -0.61    0.16

The overhang and sidefin projection factors are calculated using the following equations.


Equation 8-6

OPF = A / B



where:

OPF =    Overhang Projection Factor.

A =        Horizontal projection of overhang.

B =        Height of overhang. The vertical distance between the bottom of the overhang and the bottom of the window.

Note: Overhangs shall extend the full width of the window to receive credit for shading.


Equation 8-7

SPF = A / B




where:

SPF =    Sidefin Projection Factor.

A =        Sidefin depth, measured perpendicular to the window surface. If the left and right sidefins have different depths, then A is the average of the two depths.

B =        Distance between sidefins. If the window width is less than the sidefin spacing, then the average of the distance between the left sidefin and the right edge of the window and the distance between the right sidefin and the left edge of the window may be used. The average provides a larger SPF and, therefore, a larger sidefin credit.

Note: Sidefins shall extend the full height of the window to receive credit for shading.

A single sidefin shall receive shading credit if, for window orientations between true north and either true east or west, the sidefin is on the south side of the window. Similarly, for windows facing between true south and east or west, a single sidefin is eligible for credit if it is on the north side of the window.




Table 8-3 -- Overhang Multiplier, OHM

East, West
Overhang Projection Factor            North         and South

0.0 - 0.1    1.00    1.00
0.1 - 0.2    0.96    0.92
0.2 - 0.3    0.92    0.84
0.3 - 0.4    0.88    0.77
0.4 - 0.5    0.84    0.70
0.5 - 0.6    0.81    0.64
0.6 - 0.7    0.78    0.58
0.7 - 0.8    0.75    0.53
0.8 - 0.9    0.73    0.48
0.9 - 1.0    0.70    0.44
1.0 - 1.1    0.68    0.40
1.1 - 1.2    0.66    0.37
1.2 - 1.3    0.65    0.34
1.3 - 1.4    0.64    0.32
1.4 - 1.5    0.62    0.30

Note: Equation 8-4 for OHM may be used to provide slightly greater credit for overhangs than the values in this table.

Table 8-4 -- Sidefin Multiplier, SFM

Sidefin                    Sidefin Multiplier
Projection
Factor        North            South            East        West

0.0 - 0.1        1.00            1.00            1.00        1.00
0.1 - 0.2        0.92            0.95            0.94        0.94
0.2 - 0.3        0.85            0.90            0.88        0.88
0.3 - 0.4        0.78            0.86            0.82        0.83
0.4 - 0.5        0.72            0.82            0.76        0.78
0.5 - 0.6        0.66            0.78            0.71        0.74
0.6 - 0.7        0.61            0.74            0.67        0.69
0.7 - 0.8        0.56            0.71            0.62        0.65
0.8 - 0.9        0.52            0.68            0.58        0.62
0.9 - 1.0        0.49            0.65            0.54        0.58
1.0 - 1.1        0.46            0.62            0.51        0.55
1.1 - 1.2        0.43            0.60            0.48        0.53
1.2 - 1.3        0.41            0.57            0.45        0.50
1.3 - 1.4        0.40            0.56            0.43        0.48
1.4 - 1.5        0.39            0.54            0.40        0.47

Note: Equation 8-5 for SFM may be used to provide slightly greater credit for sidefins than the values in this table.

(2)    Exterior Shading Devices. Exterior louvers or exterior sunscreens shall be allowed for compliance in the RSHG calculations in subsection (d). In Equation 8-2 or Equation 8-3 an exterior shading device shall be described either by its shading coefficient (SCext) or by its overhang multiplier (OHM) or sidefin multiplier (SFM). Automatic or manually operable louvers shall be assumed to have an Overhang Projection Factor (for horizontal louvers) or Sidefin Projection Factor (for vertical louvers) of 1.0. Projection factors for fixed louvers and sunscreens shall be calculated as the ratio of louver width to louver spacing (see Equations 8-6 and 8-7).
(3)    Interior Shading Devices. Interior shading devices shall be allowed for compliance with the RSHG requirements in accordance with Equations 8-2 or 8-3.
(e)    Air Leakage and Comfort Ventilation. All residential buildings including hotel and motel guest rooms shall meet the requirements of subdivision (1) for comfort ventilation. In addition, conditioned spaces in residential buildings and hotel and motel guest rooms shall meet the requirements of subdivision (1) and the air leakage requirements of subdivision (2).
Conditioned spaces in commercial buildings shall comply with subdivision (2). Unconditioned spaces in commercial buildings shall comply with either subdivision (1) or subdivision (2).
(1)    Comfort Ventilation.
(A)    When compliance with this section is required under subsection (e), then habitable spaces and working spaces shall meet the following requirements. Kitchens are exempt from this section.
(i)    Louvers or door catches which allow doors to be held open shall be provided for interior doors. This requirement does not apply to hotel and motel guest room entry doors;
(ii)    A minimum of two operable openings to outside shall be provided on opposite or adjacent walls. Operable openings include operable windows, sliding glass doors, louvers and entry screen doors (if entry door is provided with door catches). For spaces with only one external wall, two windows on either side of a wing wall may be used; and
(iii)    The minimum total free area for ventilation in each space shall be equal to 12 percent of floor area. No more than 70 percent of the total free area may be placed on one wall. For spaces employing a wing wall, no more than 70 percent of the total free area may be placed on one side of the wing wall.
(B)    Exceptions.
(i)    Spaces with wiring provided for ceiling fans. In each space, a minimum of one ceiling fan outlet shall be provided for each 400 ft2 of floor area. When more than one outlet is required within a space, the outlets shall be uniformly distributed throughout the room. Wiring shall enable wall-mounted fan controls;
(ii)    Hotel/motel guest rooms that are air- conditioned;
(iii)    Spaces employing innovative natural ventilation designs which do not comply with this section, but which can be shown through analysis or demonstration to provide adequate air movement or temperature and humidity conditions for human comfort.
(2)    Air Leakage. Conditioned spaces shall meet the following criteria for minimizing air leakage.
(A)    The conditioned space shall be enclosed. Conditioning of unenclosed spaces is allowed only under the provisions of Section 32-9.3(j);
(B)    Fenestration and doors enclosing conditioned space shall be weatherstripped or otherwise tightly sealed to minimize air leakage. Operable windows shall be capable of being tightly closed. Openings which may be closed but not tightly sealed, such as jalousie windows or louvers, may account for up to 2 percent of the wall area enclosing the space;
(C)    Commercial entrances enclosing conditioned space shall be revolving or self-closing doors to minimize air leakage; and
(D)    Exterior joints, cracks and holes in building envelope components enclosing conditioned space shall be caulked, gasketed, weatherstripped or otherwise sealed to prevent air leakage.
(f)    Roof Heat Gain Factor (RHGF). The solar heat gain limits for opaque roof constructions are expressed in terms of the roof heat gain factor (RHGF) which is described in Equation 8-8. The maximum allowed limits are listed in Section 32-8.4(a).


Equation 8-8

RHGF= Ur x α x RB



where:

RHGF =    Roof Heat Gain Factor. [Btu/ft2-h-ºF].

Ur =        overall thermal transmittance value for the gross area of opaque roof surfaces, as defined in subsection (c). [Btu/ft2-h-ºF].

α =        roof surface absorptivity. Between 0.3 and 1.0 [unitless].

RB =        Radiant Barrier credit. Equals 0.33 if a radiant barrier is installed and 1.00 otherwise [unitless]. Radiant barrier installation shall comply with subsection (g) to qualify for credit.

(g)    Radiant Barrier Eligibility. To qualify for the radiant barrier credit (RB) described in subsection (f), the installation of the radiant barrier shall meet the following criteria:
(1)    The emissivity of the radiant barrier shall be less than or equal to 0.10. The manufacturer shall provide test data or documentation of the emissivity using ASTM E-408, Test Method for Total Normal Emittances of Surfaces Using Inspection Meter Techniques, ASTM Philadelphia, PA 19103.
(2)    The radiant barrier shall be securely installed in a permanent manner using one of the following five installation methods.
(A)    Draped with the shiny side facing down over the top cord of the truss before the roof deck is installed. A minimum air gap of 3/4 inch shall be provided between the radiant barrier and the roof deck above at the center of the span. A minimum 3/4-inch air gap shall also be provided between the radiant barrier and the ceiling or insulation below.
(B)    Stretched with the shiny side facing down between the top cords of the truss and stapled or otherwise secured at each side. A minimum air space of 3/4 inch above and below is required.
(C)    Stapled or otherwise secured to the bottom surface of the top cord of the truss and draped below with the shiny side facing down. For attic installations only. A minimum air space of 3/4 inch above and below is required.
(D)    Laid on top of the roof deck with the shiny side facing up and a minimum 3/4-inch air gap between the radiant barrier and the roofing material above. For open beam ceiling construction only. The roof slope shall be greater than or equal to 14 degrees from horizontal.
(E)    Laminated to the underside of the roof sheathing with at least 3/4-inch air space below.
(3)    At least one square foot of free area for ventilation shall be provided per 150 square feet of attic floor area, or in the case of vaulted or open beam ceilings, per 150 square feet of ceiling area. In vaulted or open beam ceilings, the air space shall be vented with vent area approximately evenly distributed between the top and the bottom. In vaulted ceilings, vents shall be provided for each air space between rafters.
(Added by Ord. 94-75; Am. Ord. 01-47)

Sec. 32-8.4    Prescriptive criteria.
(a) Opaque Roof Surfaces.
(1)    The roof heat gain factor (RHGF) for opaque roofs shall be less than 0.05 when calculated as described in Section 32-8.3(f).
(2)    Exception. Roofs which are completely shaded from direct sunlight or attics with one square foot of free area for ventilation per ten square feet of attic floor area shall be exempt from the requirement in subsection (a).
(b)    Opaque Wall Surfaces.
(1)    The overall thermal transmittance value (Uo) for the gross area of opaque wall surfaces, as defined in Section 32-8.3, shall be less than or equal to 0.15 for metal framed walls and 0.10 for all others. Alternatively, the R-value of insulation shall be greater than or equal to R-11.
(2)    Exceptions.
(A)    Walls with a heat capacity greater than 7.5 Btu/ºF-ft2 of wall surface area;
(B)    Portions of opaque walls completely shaded from direct sunlight by an overhang, adjacent building or feature of the landscape such as a hill or cliff. The wall must be shaded all day, throughout the year;
(C)    Walls shaded by overhangs with a projection factor greater than or equal to 0.2 on north facing walls or 0.3 on all other orientations. The projection factor equals the ratio of the horizontal projection of the overhang to the height of the wall (measured as the vertical distance from the bottom of the wall to the bottom outer edge of the overhang);
(D)    Walls enclosing spaces which are not air-conditioned.
(c)    Vertical Glazing.
(1)    The relative solar heat gain (RSHG) of vertical fenestration, as defined in Section 32-8.3(d), shall be less than or equal to the appropriate value in Table 8-6. The maximum RSHG for north orientations shall be based on the window-to-wall ratio (WWR) for north-facing walls. The maximum RSHG for all other orientations shall be based on the combined WWR for east, west and south walls. Linear interpolation may be used to determine the maximum allowed RSHG for WWR's which lie within one of the ranges.
(2)    Exceptions.
(A)    A window area of up to 2 percent of gross exterior wall area may exceed the RSHG limits for any given orientation;
(B)    Individual windows may exceed the maximum RSHG limit as long as the area-weighted average RSHG's for both the north orientation and the combined east, west and south orientations are less than or equal to the maximum limit.
(C)    Individual windows completely shaded from the sun are exempt from the RSHG limits and shall be excluded from the window area calculation.

     Table 8-6 -- Maximum Relative Solar Heat Gain (RSHG)
    for High-Rise Residential and Nonresidential Buildings

East, West
North             and South

WWR Range                Max. RSHG         Max. RSHG

0 - 0.15                    0.85                0.65
0.15 - 0.30                0.85                0.45
0.30 - 0.45                0.65                0.30
0.45 - 0.60                0.50                0.25
0.60 - 0.75                0.40                0.20
0.75 - 1.00                0.40                0.20

(d)    Horizontal Glazing (Skylights). The horizontal projection of skylight area shall be limited to a maximum fraction of the horizontal projection of roof area which is specified by the following equation:


Equation 8-9

A = 0.025 / SC


where:

A =    Maximum allowed skylight area measured as the skylight's horizontal projection. Expressed as a fraction of the horizontal projection of roof area. Shall be less than or equal to 0.15.

SC =    Shading coefficient of skylight; may be from manufacturer's literature.

(Added by Ord. 94-75; Am. Ord. 01-47)

Sec. 32-8.5    Systems performance criteria.
(a)    Purpose. This section provides a systems approach to compliance with the wall and window requirements of this code. This section may be used instead of Sections 32-8.3(b) and 32-8.3(c).
(b)    Compliance.
(1)    Walls of the building envelope are in compliance with this subsection when the annual cooling energy flux (ACEF) attributable to transmission and solar gain for the proposed design is less than the ACEF of the reference design. The ACEF shall be calculated using the methods of subsection (c).
(2)    The reference building and proposed design are defined as follows:
Surface Areas and Orientation. Walls of the reference building shall have the same gross surface areas and orientations as walls in the proposed design. Glazing area and orientation of the reference building shall be identical to the proposed design.
Shading Coefficients (SCx). The shading coefficient of glazing in the reference building shall be equal to the relative solar heat gain requirements of Section 32-8.4(c) for each window orientation.
Projection Factor (PF). The projection factor of the reference building shall be zero (no overhangs) for all window orientations.
Visible Transmittance (VT). The visible transmittance of glazing in the reference building shall be equal to the RSHG requirement of Section 32-8.4(c) for each orientation minus 0.25. The visible transmittance shall not be less than zero.
Glazing Thermal Transmittance (Uof). The glazing thermal transmittance in the reference building shall be equal to 1.21 Btu/h-ft2-ºF.
Opaque Wall Thermal Transmittance (Wall Uo). The thermal transmittance of opaque wall surfaces in the reference building shall be equal to the requirement specified in Section 32-8.4(b) for all orientations.
Wall Heat Capacity (HC). Wall heat capacity in the reference design shall be equal to 1.0.
Equipment Power Density (EQUIP). The equipment power density in W/ft2 of the reference building shall be equal to that in the proposed design. The equipment power density in the proposed design is the average receptacle power density in W/ft2, considering diversity, in the activity areas within 15 feet of each exterior wall.
If the equipment power density is not known for the proposed design, use a value from Table 13-2 for both the reference building and the proposed design. If the building occupancy is not known, use 0.5 W/ft2 for both the reference design and the proposed design.
Lighting Power Density (LIGHTS). The lighting power density in W/ft2 of the reference building shall be equal to that in the proposed design. The lighting power density in the proposed design is the average for activity areas within 15 feet of each exterior wall.
If the lighting power density is not known for the proposed design, select a value from Table 6-5 for both the reference building and the proposed design. If the building occupancy is not known, use 1.5 W/ft2 for both the reference building and the proposed design.
Daylighting Control Factor (DLCF). The daylighting control factor (DLCF) for the reference design shall be determined from Equation 8-10 for each orientation. The DLCF for the reference design shall not be greater than 1.0.


Equation 8-10

DLCFref = WWRprop x 1.67



where:

DLCFref =    The daylighting control factor (DLCF) for the reference building.

WWRprop =    The window wall ratio of the proposed design for each orientation.

The daylighting control factor (DLCF) for the proposed design shall be equal to the ratio of daylighted perimeter to total perimeter and shall be calculated separately for each orientation. The daylighted perimeter includes the width of windows and as much as three feet of wall to the left and right of windows. This may be determined from Equation 8-11. The DLCF for the proposed design shall not be greater than 1.0.


Equation 8-11

DLCFprop = Σ (Pw + Pwr + Pwl) / Pt



where:

DLCFprop =    Daylighting control factor for the proposed design for each orientation.

Pw =        Width of each window on each orientation.

Pwr =        Daylighted area to the right of each window on each orientation. This shall be the lesser of three feet, half the distance to the next window or the distance to a wall in the room or space that is perpendicular to the building perimeter.

Pwl =        Daylighted area to the left of each window on each orientation. Similar to Pwr.

Pt =        The total perimeter on each orientation.

Loads from Occupants. Sensible load from occupants in the reference building shall be equal to that of the proposed design. The default is 0.6 W/ft2.
(c)    Equation for Annual Cooling Energy Flux (ACEF). This section contains the external wall equation for use in determining external wall cumulative annual cooling energy flux and for determining compliance with the systems performance method of this section.
Seven individual terms are identified that correlate variables with physical meaning such as U-values, internal gains, and weather-related variables.

CLU,        
CLUO,
CLXUO:    Terms that correlate the cumulative annual cooling loads with the thermal transmittance of the wall.

CLM:        Term that correlates the cumulative annual cooling loads with the heat capacity of the wall.

CLG:        Term that correlates the cumulative annual cooling loads with the internal gains from occupant light and equipment.

CLS:        Term that correlates the cumulative annual cooling loads with the incident solar gains.

CLC:        Term that correlates the cumulative annual cooling loads with the climate variables for a specific location.

(1)    Cooling Equation.


Equation 8-12

WCc or Cl = Σ [CLUOi + CLXUOi
+ CLGi + CLSi + CLCi + Σ(CLUi,j + CLMi,j )]



If WCc or C1 < 0.0, then WCc or C1 is set equal to 0.0.

where:

Subscripts

i =     matrix consideration for each given orientation.

j =     matrix consideration for each wall mass construction type for the given orientation.

Indices

m =    number of wall construction types per orientation.

n =    number of wall orientations.

Variables

CLUOi =    FCi x UOCi[CUO1i x EAi x VSi x CDD50 + CUO2i x Gi + CUO3i x Gi2 x EAi2 x VSi x CDD50 + CUO4i x Gi2 x EAi2 x VSi x CDD65]

CLXUOi =    FCi(1/UOCi)[CXUO1i x EAi x VSi x CDD50 + CXUO2i x EAi(VSi x CDD50)2 + CXUO3i x Gi x CDD50 + CXUO4i x Gi2 x EAi2 x VSi x CDD50 + CXUO5i x Gi2 x CDD65]

CLGi =    FCi{Gi[CG1i + CG2i x CDD50 + CG3i x EAi(VSi x CDD50)2 + CG4i x EAi2 x VSi x CDD50 + CG5i x CDD65 + CG6i x CDD503 + CG7i x CDD653] + Gi2[CG8i x EAi x VSi x CDD50 + CG9i x EAi2 x VSi x CDD50]}

CLSi =    FCi{EAi[CS1i + CS2i x VSi x CDD50 + CS3i(VSi x CDD50)2 + CS4i x VSi x CDD65 + CS5i(VSi x CDD65)2] + EAi2[CS6i + CS7i(VSi x CDD65)2]}

CLCi =    FCi[CC1i x CDD50 + CC2i x CDD502 + CC3i x CDH80 + CC4i x CDH802 + CC5i x CDD65 + CC6i(VSi x CDD65)2 + CC7i x VSi x CDD50 + CC8i(VSi x CDD50)2 + CC9i(VSi x CDH80)2 + CC10i x VSi + CC11i x DR + CC12i x DR2 + CC13i]

CLUi,j =    FOi,j x Uow,i[CU1i x CDH80 + CU2i x CDH802 + CU3i(VSi x CDH80)2 + CU4i x DR]

CLMi,j =     FOi,j x CMCi,j[CM1i + CM2i x EAi x VSi x CDD50 + CM3i x EAi x VSi x CDD65 + CM4i x EAi2 x VSi x CDD50 + CM5i x Gi2 x CDD65 + CM6i x Gi x CDD50 + CM7i x Gi x CDD65 + CM8i x Gi x EAi x VSi x CDD50]

Note:    The coefficients for various orientations in the above equations are shown in Table 8-8.

Climate data

CDD50 =    Cooling degree-days base 50ºF.

CDD65 =    Cooling degree-days base 65ºF.

CDH80 =    Cooling degree-hours base 80ºF.

DR =        average daily temperature range for warmest month.

VSi =    annual average daily incident solar energy on facade under consideration, Btu/(ft2-day).

Building Data

FCi =    ratio, wall area (opaque and glazed) of zone under consideration divided by total wall area (opaque and glazed) of all zones.

FOi,j =    ratio, opaque wall area of zone under consideration divided by total wall area (opaque and glazed) of all zones. If multiple mass constructions are present, the FOi,j is calculated for each construction j and used to form the area weighted mass correction.

Uow,i =    area average U-value of opaque walls (including those of mass construction) in zone under consideration, Btu/(h-ft2-ºF).

UOCi =    area average U-value of wall (opaque and glazed, evaluated under cooling conditions) in zone under consideration, Btu/(h-ft2-ºF).

WWRi =    window wall ratio for zone under consideration; defined as fenestration area divided by total wall area (opaque and glazed).

EAi =    effective aperture fraction for zone under consideration, where:


Equation 8-13

EAi = WWRi x RSHGi



and

RSHGi =    the relative solar heat gain for the fenestration in a given orientation, as determined from Section 32-8.3(d).

Internal Load


Equation 8-14

Gi = Ep,i + Lp,i (1 - Rc,i x Kd,i ) + Ol,i



where:

Gi =    effective internal gain (W/ft2) for zone under consideration.

Ep,i =    equipment power, from subsection (b).

Lp,i =    lighting power, from subsection (b).

Ol,i =    occupant load adjustment, from subsection (b).

Rc,i =    for a specified orientation, the ratio of the daylighting area of the space to the total area of the space.


Equation 8-15

Kd,i = 5.871(WWRi x VLTi x OHMi ) - 13.311(WWRi x VLTi x OHMi )2



If WWRi x VLTi x OHMi is greater than 0.22, then Kd,i is set equal to 0.647.

where:

WWRi =    as defined above under Building Data.

VLTi =    visible light transmittance of the glazing material, as defined in subsection (b).

OHMi =    Overhang multiplier, from Section 32-8.3(d).

CMCi,j =    mass correction from Eq 8-16. If multiple mass constructions are present, then each CMCi,j is evaluated separately and combined by area weighting. If the U-value of the mass wall is greater than 0.40, then Uow = 0.4 shall be used to calculate the CMCi,j. If the value of HC is greater than 20, then HC = 20 shall be used to calculate the CMCi,j.

(2)    Cooling Delta Load Factor Equations. Equation 8-16 is used to predict the Cooling Delta Load Factor values.


Equation 8-16

CMC = Cooling Delta Load Factor =

[1 - e-CP1(HC-1)]




x
OLE Object Here



x


where:

HC =        Wall Heat Capacity (Btu/ft2-ºF).

U =        Wall U-Value (Btu/h-ft2-ºF).

A =        (Cooling degree-hours base 80ºF)/10,000 + 2 (ºF-h).

B =        (Daily Range)/10 + 1(ºF).

CP1 =    C5

CP2 =    C15/B3 + C16/(A2B2) + C17

CP3 =    C1/A3 + C2B3 + C3/(A2B) + C4

CP4 =    C12/(A2B2) + C13/B3 + C14

CP5 =    C18

CP6 =    C6B LN(A) + C7

LN =        Natural Logarithm

CP7 =    C19/(A2B2) + C20/(AB) + C21A2/B + C22

CP8 =    C8/(A2B2) + C9/(AB) + C10/(A2B) + C11

The coefficients C1 through C22 are taken from Table 8-7.




Table 8-7 -- Cooling Delta Load Coefficients



Insulation Position

Coefficient    Exterior    Integral    Interior

C1    220.724503    139.105667    181.616776
C2    -.056589    -.033991    -.055196
C3    -118.835388    -10.326704    -34.158966
C4    -13.674420    -20.867386    -25.591934
C5    .236381    .283882    .081029
C6    .959588    .305851    1.418998
C7    -.255004    .022622    .432421
C8    -905.677979    -307.943848    -1882.926758
C9    425.191895    80.209610    443.195801
C10    -2.510600    .049955    .430200
C11    -43.387955    -5.989545    -28.285065
C12    -259.723389    -11.396114    -63.562256
C13    -33.975525    .366851    20.844650
C14    20.488235    30.253494    9.817521
C15    -26.209152    8.833706    24.459824
C16    -241.173386    -22.254623    -70.337494
C17    18.897781    29.329697    9.884280
C18    -.353790    -.023878    -.114646
C19    156.305634    63.322754    326.344727
C20    -74.098999    -16.334656    -77.635498
C21    .445363    -.011114    -.074788
C22    7.496696    1.295576    5.204088




Table 8-8


Cooling
Coefficients     North             East             South             West

CU1    0.001539    0.003315    0.003153    0.00321
CU2    -0.308548E-07    -0.896618E-07    -0.712993E-07    -0.810530E-07
CU3    0.799493E-13    0.379280E-13    0.183083E-13    0.339810E-13
CU4    -0.079647    0.163114    0.286458    0.11178

CM1    0.32314    0.515262    0.71477    0.752643
CM2    0.153060E-05    0.138197E-05    0.161630E-05    0.142228E-05
CM3    -0.204322E-05    -0.160240E-05    -0.211063E-05    -0.197938E-05
CM4    -0.753665E-06    -0.767849E-06    -0.664430E-06    -0.740067E-06
CM5    -0.100472E-05    0    0.801057E-05    0.315193E-05
CM6    0.366708E-04    0.356503E-04    0.448106E-04    0.296012E-04
CM7    -0.673045E-04    -0.640938E-04    -0.000119    -0.766719E-04
CM8    -0.238335E-07    -0.472534E-07    -0.497469E-07    0

CUO1    -0.651094E-05    -0.838669E-05    -0.888996E-05    -0.756465E-05
CUO2    -1.040207    -1.507235    -1.512625    -1.238545
CUO3    -0.438254E-05    -0.278828E-05    -0.231352E-05    -0.412567E-05
CUO4    0.126580E-04    0.809874E-05    0.736219E-05    0.106712E-04

CXUO1    0.103744E-05    0.119338E-05    0.118588E-05    0.123251E-05
CXUO2    -0.132180E-12    -0.134656E-12    -0.116252E-12    -0.130002E-12
CXUO3    0.275554E-04    0.202621E-04    0.202365E-04    0.236964E-04
CXUO4    0.974090E-07    0.117514E-06    0.939207E-07    0.136276E-06
CXUO5    -0.118247E-04    -0.909694E-05    -0.909192E-05    -0.111077E-04

CG1    0.891286    0.583388    0.393756    0.948654
CG2    0.001479    0.001931    0.002081    0.001662
CG3    -0.552042E-12    -0.282139E-12    -0.284766E-12    -0.455720E-12
CG4    0.252311E-05    0.370821E-05    0.430536E-05    0.591511E-05
CG5    -0.001151    -0.001745    -0.001864    -0.00153
CG6    0.195243E-11    0    -0.296055E-11    0.316358E-11
CG7    -0.835805E-11    0.101089E-10    0.330027E-10    0
CG8    0.141022E-05    0.753875E-06    0.713300E-06    0.970752E-06
CG9    -0.238887E-05    -0.164961E-05    -0.163927E-05    -0.197363E-05

CS1    46.9871    33.9683    18.32016    29.3089
CS2    0.348091E-04    0.374118E-04    0.340490E-04    0.502498E-04
CS3    0    0    0.271313E-11    0
CS4    -0.166409E-04    0.694779E-05    -0.282181E-04    -0.277158E-04
CS5    0.842765E-11    0    -0.304677E-11    0.291137E-11
CS6    -56.5446    0    26.9954    14.9771
CS7    -0.134764E-10    -0.588097E-11    -0.650089E-11    -0.789218E-11

CC1    0.002747    0    0.010349    0.001865
CC2    0    0.318928E-06    -0.304413E-06    0
CC3    -0.000348    0.000319    0.00024    0.000565
CC4    0.122123E-07    -0.775318E-07    -0.271443E-07    -0.544380E-07


CC5    0.012112    0.011894    0.013248    0.009236
CC6    0.104027E-11    -0.622661E-12    -0.205178E-11    0
CC7    -0.124013E-04    -0.706280E-05    -0.165377E-04    -0.602685E-05
CC8    0    0    0.820869E-12    0
CC9    -0.375797E-13    0.606235E-13    0.197598E-13    0.389425E-13
CC10    0.030056    0.023121    0.0265    0.01704
CC11    0    0    -0.271026    -0.244274
CC12    0.002138    0.001103    0.006368    0.007323
CC13    -12.8674    -13.16522    -18.271    -10.1285


(Sec. 32-8.6    Notice to owner of cost of insulation or radiant barrier. Repealed by Ord. 01-46.)

Sec. 32-8.6    Reserved.

     Article 9. Heating, Ventilating and Air Conditioning
    (HVAC) Systems

Sections:
32-9.1    Scope.
32-9.2    General.
32-9.3    Basic requirements.
32-9.4    Prescriptive criteria.

Sec. 32-9.1    Scope.
(a)    The requirements of this article apply to all new HVAC systems or system components in both new and existing buildings.
(b)    Exception. This article does not apply to the maintenance and repair of existing systems.
(Added by Ord. 94-75)

Sec. 32-9.2    General.
The requirements in this article represent minimum design criteria. Where applicable, the state department of health (DOH) Administrative Rules, Title 11, Chapter 39, enforced by the DOH, shall apply to ventilation and air conditioning. (Added by Ord. 94-75)

Sec. 32-9.3    Basic requirements.
(a)    Load Calculations.
(1)    Calculation Procedures. Cooling system design loads for the purpose of sizing systems and equipment shall be determined in accordance with the procedures described in the ASHRAE Handbook, 1989 Fundamentals or a similar computation procedure. For those design parameters addressed in (2) through (9), the values specified shall be used.
(2)    Indoor Design Conditions. Indoor design temperature and humidity conditions for general comfort applications shall be in accordance with the comfort criteria established in ANSI/ASHRAE Standard 55-1981 Thermal Environmental Conditions for Human Occupancy, or Chapter 8 of the ASHRAE Handbook, 1989 Fundamentals, or both, except that winter humidification and summer dehumidification are not required.
(3)    Outdoor Design Conditions. Outdoor design conditions shall be selected from "Climatic Data for Region X Arizona, California, Hawaii, Nevada," Golden Gate and Southern California Chapters, ASHRAE, Fifth Edition, May 1982, or from data obtained from the National Climatic Center or a similar recognized weather data source. Cooling design temperatures shall be no greater than the 0.5 percent annualized value.
(4)    Ventilation. Outdoor air ventilation loads shall be based on ventilation rates specified in subsection (f).
(5)    Envelope. Envelope cooling loads shall be based on envelope characteristics, such as thermal conductance, shading coefficient, and air leakage, consistent with the values used to demonstrate compliance with Article 8.
(6)    Lighting. Lighting loads shall be based on actual design lighting levels or power budgets consistent with Article 6.
(7)    Other Loads. Other HVAC system loads, such as those due to people and equipment, shall be based on design data compiled from one or more of the following sources:
(A)    Actual information based on the intended use of the building;
(B)    Published data from manufacturers' technical publications;


(C)    Technical society publications such as the ASHRAE Handbooks, 1991 HVAC Applications and 1992 HVAC Systems and Equipment;
(D)    Alereza, "Estimates of recommended heat gains due to commercial appliances and equipment,"
ASHRAE Transactions, Vol. 90, Pt 2A, pp. 25-58, 1984.
(E)    Default values to be used in determining the design energy budget in Article 13 are taken from Tables 13-1, 13-2, and 13-4;
(F)    Other data based on designer's experience of loads and occupancy patterns.
(8)    Safety Factor. Design loads may, at the designer's option, be increased by as much as 10 percent to account for unexpected loads or changes in space usage.
(9)    Pickup Loads. Transient loads such as cool-down loads which occur after off-hour setback or shutoff, may be calculated from basic principles, based on the heat capacity of the building and its contents, the level of setback, and desired recovery time, or may be assumed to be up to l0 percent of the steady-state cooling design loads. The steady-state load may include a safety factor in accordance with subdivision (8).
(b)    Separate Air Distribution Systems.
(1)    Zones with special process temperature requirements, humidity requirements, or both, shall be served by separate air distribution systems from those serving zones requiring only comfort conditions, or shall include supplementary provisions so that the primary systems may be specifically controlled for comfort purposes only.
(2)    Exception. Zones that require only comfort cooling and are served by a system primarily used for process temperature and humidity control, need not be served by a separate system if the total supply air to these comfort zones is no more than 25 percent of the total system supply air, or the total conditioned floor area of the zones is less than 1,000 ft2.
(c)    Temperature Controls.
(1)    System Control. Each HVAC system shall include at least one temperature control device.
(2)    Zone Controls.
(A)    The supply of cooling energy to each zone shall be controlled by individual thermostatic controls responding to temperature within the zone.
(B)    Exceptions.
(i)    Independent perimeter systems that are designed to offset only envelope heat gains may serve one or more zones also served by an interior system, with the following limitations:
1.    The perimeter system shall include at least one thermostatic control zone for each building exposure having exterior walls facing only one orientation for 50 contiguous feet or more;
2.    The perimeter system cooling supply shall be controlled by thermostat located within the zone served by the system.
(ii)    A dwelling unit may be considered a single zone.
(3)    Thermostats shall be shaded from direct solar radiation and shall be isolated from heat gain due to large equipment and machinery.
(4)    Where used to control comfort cooling, zone thermostatic controls shall be capable of being set, locally or remotely, by adjustment or selection of sensors, up to 85 degrees Fahrenheit or higher.
(d)    Off-hour and Interlock Controls.
(1)    Off-hour Controls.
(A)    HVAC systems shall be equipped with automatic controls capable of accomplishing a reduction of energy use through control setback or equipment shutdown during periods of nonuse or alternate use of the spaces served by the system.
(B)    Exceptions.
(i)    Systems serving areas expected to operate continuously;
(ii)    Where it can be shown that setback or shutdown will not result in a decrease in overall building energy costs;
(iii)    Equipment with full load demands of 2 kW (6826 Btu/hr) or less may be controlled by readily accessible manual off-hour controls;
(iv)    Where process conditioning is required on a 24-hour basis.
(2)    Systems that serve zones which can be expected to operate non-simultaneously for more than 750 hours per year shall include isolation devices and controls to shut off or set back the supply of cooling to each zone independently. Isolation is not required for zones expected to operate continuously or expected to be inoperative only when all other zones are inoperative.
For buildings where occupancy patterns are not known at the time of system design, such as speculative buildings, isolation areas may be predesignated.
Zones may be grouped into a single isolation area provided that the total conditioned floor area does not exceed 25,000 ft2 per group nor include more than one floor.
(3)    Operable doors leading from a conditioned space to a balcony or patio in hotel or motel guest rooms shall be provided with interlock controls to disable cooling of the space while the door is open.
(e)    Dehumidification. Where a humidistat is used for comfort dehumidification, it shall be capable of being set to prevent the use of fossil fuel or electricity to reduce relative humidities below 60 percent.
(f)    Ventilation.
(1)    Outdoor air ventilation rates shall not exceed the minimum rates required by ASHRAE Standard 62-1989 by more than 10 percent.
(2)    Exception. Outdoor air quantities may be greater if required because of special occupancy or process requirements, source control of air contamination or local codes, or if it can be shown that the additional outside air does not increase overall building energy costs.
(g)    Materials and Construction.
(1)    Insulation required by subdivisions (2) and (3) shall be suitably protected from damage. Insulation should be installed in accordance with MICA Commercial and Industrial Insulation Standards, 1983.
(2)    Piping Insulation.
(A)    All HVAC system piping shall be thermally insulated in accordance with Table 9-1.
(B)    Exceptions. Piping insulation shall not be required in any of the following cases:
(i)    Factory installed piping within HVAC equipment tested and rated in accordance with Section 32-10.3;
(ii)    Piping that conveys fluids which have a design operating temperature range between 55 degrees Fahrenheit and 105 degrees Fahrenheit;
(iii)    Piping that conveys fluids which have not been heated or cooled through the use of fossil fuels or electricity;
(iv)    Where it can be shown that the heat gain and/or heat loss to or from piping without insulation will not increase building energy costs.





Table 9-1 -- Minimum Pipe Insulation (Inches) a


     Insulation
     Conductivity
Fluid                            Nominal Pipe Diameter (in)
Design        Cond.        Mean
Operating    Range,        Rating
Temp.,        Btu·in/        Temp., Runouts b 1 and 1.25 2.5 5 8
Range °F     h·ft 3 °F         °F     up to 2 less to 2 to 4 & 6 and up

    Heating Systems (Steam, Steam Condensate, and Hot Water)
Above 350    0.32-0.34    250    1.5    2.5    2.5    3.0    3.5     3.5
251-350    0.29-0.31    200    1.5    2.0    2.5    2.5    3.5     3.5
201-250    0.27-0.30    150    1.0    1.5    1.5    2.0    2.0     3.5
141-200    0.25-0.29    125    0.5    1.5    1.5    1.5    1.5     1.5
105-140    0.24-0.28    100    0.5    1.0    1.0    1.0    1.5     1.5

    Domestic and Service Hot Waterc
105 and    0.24-0.28    100    0.5    1.0    1.0    1.5    1.5     1.5
Greater

    Cooling Systems (Chilled Water, Brine & Refrigerant)d
40-55    0.23-0.27    75    0.5    0.5    0.75    1.0    1.0     1.0
Below 40    0.23-0.27    75    1.0    1.0    1.5    1.5    1.5    1.5

a.    For minimum thicknesses of alternative insulation types, see Section 32-9.3(g)(2).

b.    Runouts to individual terminal units not exceeding 12 feet in length.

c.    Applies to recirculation sections of service or domestic hot water systems and first 8 feet from storage tank for nonrecirculating systems.

d.    The required minimum thicknesses do not consider water vapor transmission and condensation. Additional insulation and/or vapor retarders may be required to limit water vapor transmission and condensation.

Alternative Insulation Types. Insulation thicknesses in Table 9-1 are based on insulation with thermal conductivities within the range listed in Table 9-l for each fluid operating temperature range, rated in accordance with ASTM C 335-84 at the mean temperature listed in the table. For insulation that has a conductivity outside the range shown in Table 9-l, for the applicable fluid operating temperature range at the mean rating temperature shown, when rounded to the nearest 1/100th Btu·inch/h·°F·ft2, the minimum thicknesses shall be determined in accordance with Equation 9-1:


Equation 9-1

T = PR [(1 + t / PR)K/k - 1]



where:

T =    minimum insulation thickness for material with conductivity K, inches.

PR =    pipe actual outside radius, in.

t =    insulation thickness from Table 9-1, in.

K =    conductivity of alternate material at the mean rating temperature indicated in Table 9-1 for the applicable fluid temperature range, Btu·in/h·°F·ft2.

k =    the lower value of the conductivity range listed in Table 9-1 for the applicable fluid temperature range, Btu·in/h·°F·ft2.

(3)    Air Handling System Insulation.
(A)    All air handling ducts and plenums installed as part of an HVAC air distribution system shall be thermally insulated in accordance with Table 9-2.
(B)    Exceptions.
(i)    Factory installed plenums, casings, or ductwork furnished as a part of HVAC equipment tested and rated in accordance with Section 32-10.3.
(ii)    Where it can be shown that the heat gain to or heat loss from ducts without insulation will not increase building energy costs.





Table 9-2 -- Minimum Duct Insulation a


Temperature        Insulation
Differenceb          R-valuec
°F            ft 2 ·h·°F/Btu

Exterior of Building                 all             8.0

Inside of building envelope in          < 15        Not Required
conditioned or unconditioned             > 15 to < 40         3.3
spacese                         > 40         5.0d

a.    Insulation R-values shown are for the insulation as installed and do not include film resistance. The required minimum thicknesses do not consider water vapor transmission and condensation. Additional insulation and/or vapor retarders may be required to limit vapor transmission and condensation. Where exterior walls are used as plenum walls, wall insulation shall be as required by the most restrictive conditions of this article or Article 8.

b.    Temperature difference is at design conditions (see Section 32-9.3(a)) between the space within which the duct is located and the design air temperature in the duct.

c.    Insulation resistance measured on a horizontal plane in accordance with ASTM C518-85 at a mean temperature of 75 degrees Fahrenheit at the installed insulation thickness.

d.    Insulation resistance for runouts to terminal devices less than 10 feet in length need not exceed 3.3 ft2·h·°F/Btu.

e.    Unconditioned spaces include crawl spaces and attics.

(4)    Duct Construction.
(A)    All air handling ductwork and plenums shall be constructed and erected in accordance with the following SMACNA publications:
(i)    HVAC Duct Construction Standards -- Metal and Flexible, 1985;
(ii)    HVAC Duct Leakage Test Manual, 1985;
(iii)    TIMA Fibrous Glass Duct Construction Standards, 1989.
(B)    In addition to the above-referenced standards, the following are required:
(i)    Leakage Tests. Ductwork which is intended to operate at static pressures in excess of 3 in. wc shall be leak-tested and be in conformance with sections of the HVAC Duct Leakage Test Manual, as follows: Test procedures shall be in accordance with those outlined in Section 5 of the manual, or equivalent; test reports shall be provided in accordance with Section 6 of the manual, or equivalent; the tested duct leakage class at a test pressure equal to the design duct pressure class rating shall be equal to or less than Leakage Class 6 as defined in Section 4.l of the manual. Leakage testing may be limited to representative sections of the duct system, but in no case shall such tested sections include less than 25 percent of the total installed duct area for the designated pressure class.
(ii)    Additional Sealing. Where supply ductwork and plenums that are intended to operate at static pressures from l/4 in. to 2 in. wc inclusive, are located outside of the conditioned space or in return plenums, joints shall be sealed in accordance with Seal Class C, as defined in the SMACNA manuals referenced above. Pressure- sensitive tape shall not be used as the primary sealant where such ducts are intended to operate at static pressures of 1 in. wc or greater.
(h)    Energy Recovery. Condenser heat recovery from air conditioning or refrigeration equipment is required for any single cooling system larger than 10 tons of cooling capacity or compressor size of greater than 15 hp for buildings with service hot water heaters with more than 75,000 Btu/h or 12 kW input rating, unless an alternative system can be shown to have a lower life-cycle cost as determined in accordance with procedures defined by the National Institute of Standards and Technology (NIST) Life-Cycle Costing Manual for the Federal Energy Management Program, NIST Handbook 135, and its supplement, Energy Price Indices and Discount Factors for Life-Cycle Cost Analysis. Assumptions used in any calculation should use the latest price indices and discount factors available at the time the calculation is submitted to the city.
(i)    Completion Requirements.
(1)    Operating and Maintenance Manual. An operating and maintenance manual shall be provided to the building owner. The manual shall include basic data relating to the operation and maintenance of HVAC systems and equipment. Required routine maintenance actions shall be clearly identified. Where applicable, HVAC control information such as diagrams, schematics, control sequence descriptions, and maintenance and calibration information shall be included.
(2)    Air System Balancing.
(A)    Air system balancing shall be accomplished in a manner to first minimize throttling losses, then fan speed shall be adjusted to meet design flow conditions. Balancing procedures shall be in accordance with those established by the National Environmental Balancing Bureau (NEBB) Procedural Standards (1983), the Association of Air Balancing Council (AABC) National Standards (1982), or equivalent procedures.
(B)    Exception. Damper throttling may be used for air system balancing with fan motors of 1 hp or less, or if throttling results in no greater than 1/3 hp fan horsepower draw above that required if the fan speed were adjusted.
(3)    Hydronic System Balancing.
(A)    Hydronic system balancing shall be accomplished in a manner to first minimize throttling losses, then the pump impeller shall be trimmed or pump speed shall be adjusted to meet flow conditions.
(B)    Exceptions. Valve throttling may be used for hydronic system balancing under any of the following conditions:
(i)    Pumps with pump motors of 10 hp or less;
(ii)    If throttling results in no greater than three (3) pump horsepower draw above that required if the impeller were trimmed;
(iii)    To reserve additional pump pressure capability in open-circuit piping systems subject to fouling. Valve throttling pressure drop shall not exceed that expected for future fouling;
(iv)    Where it can be shown that throttling will not increase overall building energy costs.
(j)    Cooling of Unenclosed Spaces.
(1)    Cooling systems for unenclosed spaces shall meet the following requirements:
(A)    Cooling system capacity shall be no greater than 20 Btu/hr per ft2 of floor area or 400 Btu/hr per occupant, whichever is greater. The estimated number of occupants shall be based on the intended average occupancy and shall not exceed the Estimated Maximum Occupancy listed in Table 2 of ASHRAE Standard 62-1989.
(B)    The floor area used to calculate the allowed cooling capacity shall be limited by a perimeter defined as follows:
(i)    The perimeter shall not extend beyond the location of the ceiling air supply diffusers or the throw of the side wall diffusers.
(ii)    The perimeter shall be set back at least 10 feet from the opening to the outside, which is defined by the outer edge of the ceiling or overhanging roof.
(iii)    The perimeter shall be bounded on at least one side by a permanent, ceiling-height physical obstruction such as a wall or fixed window.
(k)    System Commissioning.
(1)    HVAC control systems shall be tested to assure that control elements are calibrated, adjusted, and in proper working condition.
(2)    For projects larger than 50,000 ft2 (4600 m2) conditioned area, detailed instructions for commissioning HVAC systems shall be provided by the designer in plans and specifications.
(Added by Ord. 94-75; Am. Ord. 01-47)

Sec. 32-9.4    Prescriptive criteria.
(a)    System and Equipment Sizing.
(1)    HVAC systems and equipment shall be sized to provide no more than the space and system loads calculated in accordance with Section 32-9.3(a).
(2)    Exceptions.
(A)    Equipment capacity may exceed the design load, provided the equipment selected is the smallest size needed to meet the load within available options of the desired equipment line.
(B)    Equipment whose capacity exceeds the design load may be specified if oversizing the equipment can be shown to not increase the overall annual energy costs.
(C)    Standby equipment may be installed if controls and devices are provided which allow standby equipment to operate automatically only when the primary equipment is not operating.
(D)    Multiple units of the same equipment type, such as multiple chillers and boilers, with combined capacities exceeding the design load may be specified to operate concurrently only if controls are provided that sequence or otherwise optimally control the operation of each unit based on load.
(E)    For a single piece of equipment which has both heating and cooling capability, only the cooling function need meet the requirements of this section. Capacity for the heating function shall be, within available equipment options, the smallest size necessary to meet the load.
(b)    Zone Controls.
(1)    Zone thermostatic and humidistatic controls shall prevent:
(A)    Reheating;
(B)    Recooling;
(C)    Mixing or simultaneous supply of air that has been previously mechanically heated and air that has been previously cooled;
(D)    Other simultaneous operation of heating and cooling systems to the same zone.
(2)    Exceptions.
(A)    Variable air volume systems which, during periods of occupancy, are designed to reduce the air supply to each zone to a minimum before reheating, recooling, or mixing takes place. This minimum volume shall be no greater than the largest of the following:
(i)    30 percent of the peak supply volume;
(ii)    The minimum allowed to meet ventilation requirements of Section 32-9.3(f);
(iii)    0.4 cfm/ft2 of zone conditioned floor area;
(B)    Zones where special pressurization relationships or cross-contamination requirements are such that variable air volume systems are impractical, such as some areas of hospitals and laboratories;
(C)    At least 75 percent of the energy for reheating or for providing warm air in mixing systems is provided from a site-recovered or site-solar energy source;
(D)    Zones where specified humidity levels are required to satisfy process needs, such as computer rooms and museums. See Section 32-9.3(b);
(E)    Zones with a peak supply air quantity of 300 cfm or less.
(c)    Fan System Design Criteria.
(1)    General.
(A)    The following design criteria apply to all HVAC fan systems used for comfort ventilating and/or air conditioning. For the purposes of this section, the energy demand of a fan system is the sum of the demand of all fans which are required to operate at design conditions to supply air from the cooling source to the conditioned space(s) and return it to the source or exhaust it to the outdoors.
(B)    Exceptions.
(i)    Systems with total fan system motor power of l0 hp or less;
(ii)    Unitary equipment for which the energy used by the fan is considered in the efficiency ratings of Section 32-10.3;
(iii)    For the purposes of subsection (c), total fan energy demand need not include the additional power required by air treatment or filtering systems with final pressure drops in excess of 1.0 in. wc.
(2)    Constant Volume Fan Systems. For fan systems which provide a constant air volume whenever the fans are operating, the power required by the motors for the combined fan system at design conditions shall not exceed 0.8 W/cfm of supply air.
(3)    Variable Air Volume (VAV) Fan Systems.
(A)    For fan systems which are able to vary system air volume automatically as a function of load, the power required by the motors for the combined fan system shall not exceed l.25 W/cfm of supply air at design conditions.
(B)    Individual VAV fans with motors 25 hp and larger shall include controls and devices necessary for the fan motor to demand no more than 50 percent of design wattage at 50 percent of design air volume, based on manufacturer's test data.
(d)    Pumping System Design Criteria.
(1)    General.
(A)    The following design criteria apply to all HVAC pumping systems used for comfort air conditioning. For the purposes of subsection (d), the energy demand of a pumping system is the sum of the demand of all pumps which are required to operate at design conditions to supply fluid from the cooling source to the conditioned space(s) or heat transfer devices(s) and return it to the source.
(B)    Exception. Systems with total pump system motor power of 10 hp or less.
(2)    Friction Rate. Piping systems should be designed at a friction pressure loss rate of no more than 4 feet of water per 100 equivalent feet of pipe. Note: Lower friction rates may be required for proper noise or corrosion control.
(3)    Variable Flow.
(A)    Pumping systems which serve control valves designed to modulate or step open and closed as a function of load, shall be designed for variable fluid flow. The system shall be capable of reducing system flow to 50 percent of design flow or less. Flow may be varied with variable speed driven pumps or staged multiple pumps.
(B)    Exceptions.
(i)    Dedicated equipment pumps separated from modulation control valves in a primary/secondary loop arrangement. Secondary pumps shall comply with (A);
(ii)    Systems that serve no more than one control valve;
(iii)    Systems that include supply temperature reset controls in accordance with subsection (e)(2) without exception;
(iv)    Where the overall building energy costs resulting from an alternative design can be shown to be no more than those from a variable flow system.
(e)    System Temperature Reset Controls.
(1)    Air Systems.
(A)    Systems supplying cooled air to multiple zones shall include controls which automatically reset supply air temperatures by representative building loads or by outside air temperature. Temperature shall be reset by at least 25 percent of the design supply-air-to-room-air temperature difference. Zones which are expected to experience relatively constant loads, such as interior zones, shall be designed for the fully reset supply temperature.
(B)    Exceptions.
(i)    Systems which comply with subsection (b) without using exceptions (2)(A) or (2)(B);
(ii)    Where it can be shown that supply air temperature reset increases overall building annual energy costs.
(2)    Hydronic Systems.
(A)    Systems supplying chilled water to comfort air conditioning systems shall include controls which automatically reset supply water temperatures by representative building loads (including return water temperature) or by outside air temperature. Temperature shall be reset by at least 25 percent of the design supply-to-return water temperature difference.
(B)    Exceptions.
(i)    Systems that comply with subsection (d)(3) without exception;
(ii)    Where it can be shown that supply temperature reset increases overall building annual energy costs;
(iii)    Systems for which supply temperature reset controls cannot be implemented without causing improper operation of heating, cooling, humidification, or dehumidification systems;
(iv)    Systems with less than 600,000 Btu/hr design capacity.
(f)    Kitchen Hoods.
(1)    Individual kitchen exhaust hoods larger than 5000 cfm (2500 L/s) shall be provided with make-up air sized for at least 50 per cent of exhaust air volume that is uncooled or cooled without the use of mechanical cooling.
(2)    Exceptions:
(A)    Where hoods are used to exhaust ventilation air which would otherwise exfiltrate or be exhausted by other fan systems.
(B)    Certified grease extractor hoods that require a face velocity no greater than 60 fpm (18 m/s).
(Added by Ord. 94-75; Am. Ord. 01-47)


     Article 10. Heating, Ventilating and Air
    Conditioning (HVAC) Equipment


Sections:
32-10.1    Scope.
32-10.2    General.
32-10.3    Basic requirements.

Sec. 32-10.1    Scope.
(a)    The requirements of this article apply to new HVAC equipment installed in new or existing buildings.
(b)    Exception. This article does not apply to the maintenance or repair of existing HVAC equipment.
(Added by Ord. 94-75)

Sec. 32-10.2    General.
HVAC equipment shall be supplied with the information necessary to make the analysis required to determine compliance with this code.
(Added by Ord. 94-75)

Sec. 32-10.3    Basic requirements.
(a)    Mechanical Equipment Efficiency.
(1)    Equipment shown in Tables 10.1A through 10.1G shall have a minimum performance at the specified rating conditions when tested in accordance with the specified test procedure. Omission of minimum performance requirements for equipment not listed in Tables 10.1A through 10.1G does not preclude use of such equipment. Equipment not listed in Tables 10.1A through 10.1G has no minimum performance requirements. Where multiple rating conditions or performance requirements are provided, the equipment shall satisfy all stated requirements, unless otherwise exempted by footnotes in the table. However, equipment covered under the Federal Energy Policy Act of 1992 (EPACT) shall have no minimum efficiency requirements for operation at minimum capacity or other than standard rating conditions. Equipment used to provide water heating functions as part of a combination system shall satisfy all stated requirements for the appropriate space heating or cooling category.
(2)    If a certification program exists for a product covered in Tables 10.1A through 10.1G, and it includes provisions for verification and challenge of equipment efficiency ratings, then the product shall be either listed in the certification program or, alternatively, the ratings shall be verified by an independent laboratory test report. If no certification program exists for a product covered in Tables 10.1A through 10.1G, the equipment efficiency ratings shall be supported by data furnished by the manufacturer. Where components such as indoor or outdoor coils from different manufacturers are used, the system designer shall specify component efficiencies whose combined efficiency meets the minimum equipment efficiency requirements in this section.
(3)    Tables 10.1A through 10.1G contain the minimum efficiency requirements for equipment covered by this section of the standard. The tables are organized to cover the following types of equipment:
(A)    Table 10.1A Air Conditioners and Condensing Units;
(B)    Table 10.1B Heat Pumps;
(C)    Table 10.1C Water Chilling Packages;
(D)    Table 10.1D Packaged Terminal and Room Air Conditioners and Heat Pumps;
(E)    Table 10.1E Furnaces, Duct Furnaces and Unit Heaters;
(F)    Table 10.1F Boilers; and
(G)    Table 10.1G Heat Rejection Equipment.
(4)    Gas-fired and oil-fired forced air furnaces with input ratings $ 225,000 Btu/h (65 kW) shall also have an intermittent ignition or interrupted device (IID), and have either power venting or a flue damper. A vent damper is an acceptable alternative to a flue damper for furnaces where combustion air is drawn from the conditioned space. All furnaces with input ratings $ 225,000 Btu/h (65 kW), including electric furnaces, that are not located within the conditioned space shall have jacket losses not exceeding 0.75% of the input rating.
(5)    Exceptions:
(A)    Water-cooled centrifugal water-chilling packages that are not designed for operation at ARI Standard 550 test conditions (and thus cannot be tested to meet the requirements of Table 10.1C) of 44°F leaving chilled water temperature and 85°F entering condenser water temperature shall have a minimum full load COP and IPLV rating as shown in Tables 10.1H, I, and J. The table values are only applicable over the following full load design ranges:
(i)    Leaving Chiller Water Temperature: 40 to 48°F;
(ii)    Entering Condenser Water Temperature: 75 to 85°F; and
(iii)    Condensing Water Temperature Rise: 5 to 15°F.
(B)    Chillers designed to operate outside of these ranges are not covered by this standard.
(b)    Maintenance. Operation and maintenance information shall be provided with the equipment by the equipment supplier.


Table 10.1A (I-P Units)
Unitary Air Conditioners and Condensing Units, Electrically Operated,
Minimum Efficienc y Requirements


Equipment Type
 

Size Category
 

Sub-Category or Rating Condition
 

Minimum Efficiencyb
 

Test Procedure
 


Air Conditioners,
Air Cooled
 

< 65,000 Btu/hd
 

Split System
 

10.0 SEER
 

ARI 210/240
 
   
Single Package
 

9.7 SEER
 
 
 
e65,000 Btu/h and
< 135,000 Btu/h
 

Split System and
Single Package
 

10.3 EERc
10.6 IPLVc
 
 
 
e135,000 Btu/h and
< 240,000 Btu/h
 

Split System and
Single Package
 

9.7 EERc
9.9 IPLVc
 

ARI 340/360
 
 
e 240,000 Btu/h and
<760,000 Btu/h
 

Split System and
Single Package
 

9.5 EERc
9.7 IPLVc
 
 
 
e760,000 Btu/h
 

Split System and
Single Package
 

9.2 EERc
9.4 IPLVc
 
 

Air Conditioners, Water and Evaporatively Cooled
 

< 65,000 Btu/h
 

Split System and
Single Package
 

12.1 EER
11.2 IPLV
 

ARI 210/240
 
 
e 65,000 Btu/h and
< 135,000 Btu/h
 

Split System and
Single Package
 

11.5 EERc
10.6 IPLVc
 
 
 
e135,000 Btu/h and
d240,000 Btu/h
 

Split System and
Single Package
 

11.0 EERc
10.3 IPLVc
 

ARI 340/360
 
 
> 240,000 Btu/h
 

Split System and
Single Package
 

11.0 EERc
10.3 IPLVc
 
 

Condensing Units,
Air Cooled
 

e135,000 Btu/h
 

 

10.1 EER
11.2 IPLV
 

ARI 365
 

Condensing Units,
Water or Evaporatively Cooled
 

e135,000 Btu/h
 

 

13.1 EER
13.1 IPLV
 
 



b    IPLVs are only applicable to equipment with capacity modulation.

c    Deduct 0.2 from the required EERs and IPLVs for units with a heating section other than electric resistance heat.

d    Single-phase air-cooled air-conditioners < 65,000 Btu/h are regulated by NAECA. SEER values are those set by NAECA.  



Table 10.1B (I-P Units)
Unitary and Applied Heat Pumps, Electrically Operated, Minimum Efficiency Requirements


Equipment Type
 

Size Category
 

Sub-Category or Rating Condition
 

Minimum Efficiencyb
 

Test Procedure
 

Air Cooled, (Cooling Mode)
 

< 65,000 Btu/hd
 

Split System
 

10.0 SEER
 

ARI 210/240
 
   
Single Package
 

9.7 SEER
 
 
 
e65,000 Btu/h and
< 135,000 Btu/h
 

Split System and
Single Package
 

10.1 EERc
10.4 IPLVc
 
 
 
e135,000 Btu/h and
<240,000 Btu/h
 

Split System and
Single Package
 

9.3 EERc
9.5 IPLVc
 

ARI 340/360
 
 
e240,000 Btu/h
 

Split System and
Single Package
 

9.0 EERc
9.2 IPLVc
 
 

Water-Source
(Cooling Mode)
 

< 17,000 Btu/h
 

85°F Entering Water
 

 

ARI 320
 
 
 

86°F Entering Water
 

11.2 EER
 

ARI/ISO-13256-1
 
 

e 17,000 Btu/h and
<65,000 Btu/h
 

85°F Entering Water
 

 

ARI 320
 
 
 

86°F Entering Water
 

12.0 EER
 

ARI/ISO-13256-1
 
 
e65,000 Btu/h and
< 135,000 Btu/h
 

85°F Entering Water
 

 

ARI 320
 
 
 

86°F Entering Water
 

12.0 EER
 

ARI/ISO-13256-1  

Groundwater-Source
(Cooling Mode)
 

< 135,000 Btu/h
 

70°F Entering Water
50EF Entering Water
 

 

ARI 325
 
 
 

59°F Entering Water
 

16.2 EER
 

ARI/ISO-13256-1
 

Ground Source
(Cooling Mode)
 

< 135,000 Btu/h
 

77°F Entering Brine
70EF Entering Brine
 

 

ARI 330
 
 
 

77°F Entering Water
 

13.4 EER
 

ARI/ISO-13256-1
 

Air Cooled
(Heating Mode)
 

< 65,000 Btu/hd
(Cooling Capacity)
 

Split System
 

6.8 HSPF
 

ARI 210/240
 
   
Single Package
 

6.6 HSPF
 
 
 
e65,000 Btu/h and
< 135,000 Btu/h
(Cooling Capacity)
 

47°F db/43°F wb Outdoor Air
17°F db/15°F wb Outdoor Air
 

3.2 COP

2.2 COP

 
 
 
e135,000 Btu/h
(Cooling Capacity)
 

47°F db/43°F wb Outdoor Air
17°F db/15°F wb Outdoor Air
 

3.1 COP

2.0 COP

 

ARI 340/360
 

Water-Source
(Heating Mode)
 

< 135,000 Btu/h
(Cooling Capacity)
 

70°F Entering Water
 

 

ARI 320
 
 
 

68°F Entering Water
 

4.2 COP
 

ARI/ISO-13256-1
 

Groundwater-Source
(Heating Mode)
 

< 135,000 Btu/h
(Cooling Capacity)
 

70°F Entering Water
50EF Entering Water
 

 

ARI 325
 
 
 

50°F Entering Water
 

3.6 COP
 

ARI/ISO-13256-1
 

Ground Source
(Heating Mode)
 

< 135,000 Btu/h
(Cooling Capacity)
 

32°F Entering Brine
 

 

ARI 330
 
 
 

32°F Entering Water
 

3.1 COP
 

ARI/ISO-13256-1
 



b    IPLVs and Part load rating conditions are only applicable to equipment with capacity modulation.

c    Deduct 0.2 from the required EERs and IPLVs for units with a heating section other than electric resistance heat.

d    Single-phase air-cooled heat pumps < 65,000 Btu/h are regulated by NAECA. SEER and HSPF values are those set by NAECA.  




Table 10.1C (I-P Units)
Water Chilling Packages, Minimum Efficiency Requirements


Equipment Type
 

Size Category
 

Sub-Category or Rating Condition
 

Minimum Efficiencyb
 

Test Procedure
 


Air Cooled, With Condenser,
Electrically Operated
 

< 150 Tons
 

 

2.80 COP
2.80 IPLV
 

ARI 550
or
ARI 590
as appropriate
 
 
e150 Tons  
 
 
 

Air Cooled,
Without Condenser,
Electrically Operated
 

All Capacities
 

 

3.10 COP
3.10 IPLV  
 

Water Cooled,
Electrically Operated,
Positive Displacement
(Reciprocating)
 

All Capacities
 

 

4.20 COP
4.65 IPLV
 

ARI 590
 

Water Cooled,
Electrically Operated,
Positive Displacement
(Rotary Screw and Scroll)
 

< 150 Tons
 

 

4.45 COP
4.50 IPLV
 

ARI 550
or
ARI 590
as appropriate
 
 
e150 Tons and
< 300 Tons
 

 

4.90 COP
4.95 IPLV
 
 
 
e300 Tons
 

 

5.50 COP
5.60 IPLV
 
 

Water Cooled,
Electrically Operated, Centrifugal
 

< 150 Tons
 

 

5.00 COP
5.00 IPLV
 


ARI 550
 
 
e150 Tons and
< 300 Tons
 

 

5.55 COP
5.55 IPLV
 
 
 
e300 Tons
 

 

6.10 COP
6.10 IPLV
 
 

Air Cooled Absorption
Single Effect
 

All Capacities
 

 

0.60 COP
 


ARI 560

 

Water Cooled Absorption
Single Effect
 

All Capacities
 

 

0.70 COP  
 

Absorption Double Effect,
Indirect-Fired
 

All Capacities
 

 

1.00 COP
1.05 IPLV  
 

Absorption Double Effect,
Direct-Fired
 

All Capacities
 

 

1.00 COP
1.00 IPLV  
 



b    The chiller equipment requirements do not apply for chillers used in low temperature applications where the design leaving fluid temperature is less than or equal to 40°F.  

Table 10.1D (I-P Units)
Packaged Terminal Air Conditioners, Packaged Terminal Heat Pumps, Room Air Conditioners, and Room Air Conditioner Heat Pumps, Electrically Operated, Minimum Efficiency Requirements


Equipment Type
 

Size Category (Input)
 

Sub-Category or Rating Condition
 

Minimum Efficiency
 

Test Procedure
 

PTAC (Cooling Mode)
New Construction
 

All Capacities
 

95°F db Outdoor Air
 

12.5 - (0.213 x Cap/1000)b EER
 


ARI 310/380

 
   
82°F db Outdoor Air
 

14.7 - (0.213 x Cap/1000)b EER  
 

PTAC (Cooling Mode) Replacementsc
 

All Capacities
 

95°F db Outdoor Air
 

10.9 - (0.213 x Cap/1000)b EER  
 
   
82°F db Outdoor Air
 

13.1 - (0.213 x Cap/1000)b EER  
 

PTHP (Cooling Mode)
New Construction
 

All Capacities
 

95°F db Outdoor Air
 

12.3 - (0.213 x Cap/1000)b EER  
 
   
82°F db Outdoor Air
 

14.5 - (0.213 x Cap/1000)b EER  
 

PTHP (Cooling Mode)
Replacementsc
 

All Capacities
 

95°F db Outdoor Air
 

10.8 - (0.213 x Cap/1000)b EER  
 
   
82°F db Outdoor Air
 

13.0 - (0.213 x Cap/1000)b EER  
 

PTHP (Heating Mode)
New Construction
 

All Capacities
 


 

3.2 - (0.026 x Cap/1000)b COP  
 

PTHP (Heating Mode)
Replacementsc
 

All Capacities
 

 

2.9 - (0.026 x Cap/1000)b COP  
 

Room Air Conditioners, with Louvered Sides
 

< 6,000 Btu/h
 

 

9.7 EER
 

ANSI/AHAM
RAC-1
 
 
e6,000 Btu/h and
< 8,000 Btu/h
 

 

9.7 EER
 
 
 
e 8,000 Btu/h and
< 14,000 Btu/h
 

 

9.8 EER
 
 
 
e14,000 Btu/h and
< 20,000 Btu/h
 

 

9.7 EER
 
 
 
e20,000 Btu/h
 

 

8.5 EER
 
 

Room Air Conditioners, without Louvered Sides
 

< 8,000 Btu/h
 

 

9.0 EER
 
 
 
e8,000 Btu/h and
< 20,000 Btu/h
 

 

8.5 EER
 
 
 
e20,000 Btu/h
 

 

8.5 EER
 
 

Room Air Conditioner Heat Pumps with Louvered Sides
 

< 20,000 Btu/h
 

 

9.0 EER
 
 
 

e 20,000 Btu/h
 

 

8.5 EER
 
 

Room Air Conditioner Heat Pumps without Louvered Sides
 

< 14,000 Btu/h
 

 

8.5 EER
 
 
 

e 14,000 Btu/h
 

 

8.0 EER
 
 

Room Air Conditioner, Casement Only
Room Air Conditioner, Casement --Slider
 

All Capacities
 

 

8.7 EER
 
 
 
 
   
 
 

All Capacities
 

 

9.5 EER
 
 
 
     
 



b    Cap means the rated cooling capacity of the product in Btu/h. If the unit's capacity is less than 7000 Btu/h, use 7000 Btu/h in the calculation. If the unit's capacity is greater than 15,000 Btu/h, use 15,000 Btu/h in the calculation.

c    Replacement units must be factory labeled as follows: "MANUFACTURED FOR REPLACEMENT APPLICATIONS ONLY; NOT TO BE INSTALLED IN NEW CONSTRUCTION PROJECTS." Replacement efficiencies apply only to units with existing sleeves less than 16 in. high and less than 42 in. wide.
 



Table 10.1E (I-P and SI Units)
Warm Air Furnaces and Combination Warm Air Furnaces/Air-Conditioning Units,
Warm Air Duct Furnaces and Unit Heaters, Minimum Efficiency Requirements


Equipment Type
 

Size Category (Input)
 

Sub-Category or Rating Condition
 

Minimum Efficiencyd
 

Test Procedure
 

Warm Air Furnace,
Gas-Fired
 

< 225,000 Btu/h
(66 kW)
 

 

78% AFUE
or
80% Etc
 

DOE 10 CFR
Part 430 or
ANSI Z21.47
 
 
e225,000 Btu/h
(66 kW)
 

Maximum Capacityc
 

80% Ecf
 

ANSI Z21.47
 

Warm Air Furnace,
Oil-Fired
 

< 225,000 Btu/h
(66 kW)
 

 

78% AFUE
or
80% Etc
 

DOE 10 CFR
Part 430 or
UL 727
 
 
e225,000 Btu/h
(66 kW)
 

Maximum Capacityb
 

81% Etg
 

UL 727
 

Warm Air
Duct Furnaces,
Gas-Fired
 

All Capacities
 

Maximum Capacityb
 

80% Ece
 


ANSI Z83.9
 

Warm Air
Unit Heaters,
Gas-Fired
 

All Capacities
 

Maximum Capacityb
 

80% Ece
 


ANSI Z83.8
 

Warm Air
Unit Heaters,
Oil-Fired
 

All Capacities
 

Maximum Capacityb
 

80% Ece
 

UL 731
 



b    Maximum rating as provided for and allowed by the unit's controls.

c    Combination units not covered by NAECA (3-phase power or cooling capacity greater than or equal to 65,000 Btu/h [19 kW]) may comply with either rating.

d    Et = Thermal efficiency. See test procedure for detailed discussion.

e    Ec = Combustion efficiency (100% less flue losses). See test procedure for detailed discussion.

f    Ec = Combustion efficiency. Units must also include an IID, have jacket losses not exceeding 0.75% of the input rating, and have either power venting or a flue damper. A vent damper is an acceptable alternative to a flue damper for those furnaces where combustion air is drawn from the conditioned space.

g    Et = Thermal efficiency. Units must also include an IID, have jacket losses not exceeding 0.75% of the input rating, and have either power venting or a flue damper. A vent damper is an acceptable alternative to a flue damper for those furnaces where combustion air is drawn from the conditioned space.  


Table 10.1F (I-P Units)
Boilers, Gas- and Oil-Fired, Minimum Efficiency Requirements


Equipment Typef
 

Size Category
 

Sub-Category or
Rating Condition
 

Minimum Efficiencyd
 

Test Procedure
 

Boilers, Gas-Fired
 

< 300,000 Btu/h
 

Hot Water
 

80% AFUE
 

DOE 10 CFR
Part 430
 
   
Steam
 

75% AFUE
 
 
 
e300,000 Btu/h and d 2,500,000 Btu/h
 

Maximum Capacityb
 

75% Et
 


H.I. Htg Boiler Std
 
 
> 2,500,000 Btu/hf
 

Hot Water
 

80% Ec
 
 
 
> 2,500,000 Btu/hf
 

Steam
 

80% Ec
 
 

Boilers, Oil-Fired
 

< 300,000 Btu/h
 

 

80% AFUE
 

DOE 10 CFR
Part 430
 
 
e300,000 Btu/h and d 2,500,000 Btu/h
 

Maximum Capacityb
 

78% Et
 


H.I. Htg Boiler Std
 
 
> 2,500,000 Btu/hf
 

Hot Water
 

83% Ec
 
 
 
> 2,500,000 Btu/hf
 

Steam
 

83% Ec  
 

Oil-Fired (Residual)
 

e300,000 Btu/h and
d2,500,000 Btu/h
 

Maximum Capacityb
 

78% Et
 


H.I. Htg Boiler Std
 
 
> 2,500,000 Btu/hf
 

Hot Water
 

83% Ec
 
 
 
> 2,500,000 Btu/hf
 

Steam
 

83% Ec
 
 



b    Maximum rating as provided for and allowed by the unit's controls.

d    Et = Thermal efficiency. See reference document for detailed information.

f    These requirements apply to boilers with rated input of 8,000,000 Btu/h or less that are not packaged boilers, and to all packaged boilers. Minimum efficiency requirements for boilers cover all capacities of packaged boilers.  


Table 10.1G (I-P and SI Units)
Performance Requirements for Heat Rejection Equipment


Equipment Type
 

Total System Heat Rejection Capacity at Rated Conditions
 

Sub-Category or
Rating Condition
 

Required Performancea,b
 

Test Procedure
 

Propeller or Axial Fan Cooling Towers
 

All
 

95°F (35°C) Entering Water
85°F (29°C) Leaving Water
75°F (24°C) wb Outdoor Air
 

e38.2 gpm/hp
(3.23 L/s kW)
 

CTI ATC-105
and
CTI STD-201
 

Centrifugal Fan
Cooling Towers
 

All
 

95°F (35°C) Entering Water
85°F (29°C) Leaving Water
75°F (24°C) wb Outdoor Air
 

e 20.0 gpm/hp
(1.7 L/s kW)
 

CTI ATC-105
and
CTI STD-201
 

Air Cooled Condensers
 

All
 

125°F (52°C) Condensing Temperature
R22 Test Fluid
190°F (88°C) Entering Gas Temperature
15°F (8°C) Subcooling
95°F (35°C) Entering Drybulb
 

e176,000 Btu/h hp
(69 COP)
 

ARI 460
 



a    For purposes of this table, cooling tower performance is defined as the maximum flow rating of the tower divided by the fan nameplate rated motor power.

b     For purposes of this table air-cooled condenser performance is defined as the heat rejected from the refrigerant divided by the fan nameplate rated motor power.  





Table 10.1H (I-P Units)
COPs and IPLVs for Non-Standard Centrifugal Chillers d 150 Tons


Centrifugal Chillers d 150 Tons
COPstd = 5.4
 


 

Condenser Flow Rate
 


 

2 gpm/ton
 

2.5 gpm/ton
 

3 gpm/ton
 

4 gpm/ton
 

5 gpm/ton
 

6 gpm/ton
 


Leaving Chilled Water Temperature (°F)
 

Entering Condenser Water Temperature (°F)
 

LIFTa
(°F)
 


Required COP and IPLV

 

46  
75   29   6.00   6.27   6.48   6.80   7.03   7.20  
45  
75   30   5.92   6.17   6.37   6.66   6.87   7.02  
44  
75   31   5.84   6.08   6.26   6.53   6.71   6.86  
43  
75   32   5.75   5.99   6.16   6.40   6.58   6.71  
42  
75   33   5.67   5.90   6.06   6.29   6.45   6.57  
41  
75   34   5.59   5.82   5.98   6.19   6.34   6.44  
46  
80   34   5.59   5.82   5.98   6.19   6.34   6.44  
40  
75   35   5.50   5.74   5.89   6.10   6.23   6.33  
45  
80   35   5.50   5.74   5.89   6.10   6.23   6.33  
44  
80   36   5.41   5.66   5.81   6.01   6.13   6.22  
43  
80   37   5.31   5.57   5.73   5.92   6.04   6.13  
42  
80   38   5.21   5.48   5.64   5.84   5.95   6.04  
41  
80   39   5.09   5.39   5.56   5.76   5.87   5.95  
46  
85   39   5.09   5.39   5.56   5.76   5.87   5.95  
40  
80   40   4.96   5.29   5.47   5.67   5.79   5.86  
45  
85   40   4.96   5.29   5.47   5.67   5.79   5.86  
44  
85   41   4.83   5.18   5.40   5.59   5.71   5.78  
43  
85   42   4.68   5.07   5.28   5.50   5.62   5.70  
42  
85   43   4.51   4.94   5.17   5.41   5.54   5.62  
41  
85   44   4.33   4.80   5.05   5.31   5.45   5.53  
40  
85   45   4.13   4.65   4.92   5.21   5.35   5.44  


Condenser DTb  

14.04
 

11.23
 

9.36
 

7.02
 

5.62
 

4.68
 



a    LIFT = Entering Condenser Water Temperature -- Leaving Chilled Water Temperature

b     Condenser DT = Leaving Condenser Water Temperature (F) -- Entering Condenser Water Temperature (F)

Kadj = 6.1507 - 0.30244(X) + 0.0062692(X)2 - 0.000045595(X)3
where X = Condenser DT + LIFT

COPadj = Kadj * COPstd  


Table 10.1I (I-P Units)
COPs and IPLVs for Non-Standard Centrifugal Chillers
> 150 Tons, d 300 Tons



Centrifugal Chillers > 150 Tons, d 300 Tons
COPstd = 5.55
 


 

Condenser Flow Rate
 


 

2 gpm/ton
 

2.5 gpm/ton
 

3 gpm/ton
 

4 gpm/ton
 

5 gpm/ton
 

6 gpm/ton
 


Leaving Chilled Water Temperature ( F)
 

Entering Condenser Water Temperature (°F)
 

LIFTa
(°F)
 


Required COP and IPLV

 
       

46  
75   29   6.17   6.44   6.66   6.99   7.23   7.40  
45  
75   30   6.08   6.34   6.54   6.84   7.06   7.22  
44  
75   31   6.00   6.24   6.43   6.71   6.90   7.05  
43  
75   32   5.91   6.15   6.33   6.58   6.76   6.89  
42  
75   33   5.83   6.07   6.23   6.47   6.63   6.75  
41  
75   34   5.74   5.98   6.14   6.36   6.51   6.62  
46  
80   34   5.74   5.98   6.14   6.36   6.51   6.62  
40  
75   35   5.65   5.90   6.05   6.26   6.40   6.51  
45  
80   35   5.65   5.90   6.05   6.26   6.40   6.51  
44  
80   36   5.56   5.81   5.97   6.17   6.30   6.40  
43  
80   37   5.46   5.73   5.89   6.08   6.21   6.30  
42  
80   38   5.35   5.64   5.80   6.00   6.12   6.20  
41  
80   39   5.23   5.54   5.71   5.91   6.03   6.11  
46  
85   39   5.23   5.54   5.71   5.91   6.03   6.11  
40  
80   40   5.10   5.44   5.62   5.83   5.95   6.03  
45  
85   40   5.10   5.44   5.62   5.83   5.95   6.03  
44  
85   41   4.96   5.33   5.55   5.74   5.86   5.94  
43  
85   42   4.81   5.21   5.42   5.66   5.78   5.86  
42  
85   43   4.63   5.08   5.31   5.56   5.69   5.77  
41  
85   44   4.45   4.93   5.19   5.46   5.60   5.69  
40  
85   45   4.24   4.77   5.06   5.35   5.50   5.59  

Condenser DTb  
14.04  
11.23   9.36   7.02   5.62   4.68  



a    LIFT = Entering Condenser Water Temperature -- Leaving Chilled Water Temperature

b     Condenser DT = Leaving Condenser Water Temperature (F) - Entering Condenser Water Temperature (F)

Kadj = 6.1507 - 0.30244(X) + 0.0062692(X)2 - 0.000045595(X)3
where X = Condenser DT + LIFT

COPadj = Kadj * COPstd  



Table 10.1J (I-P Units)
COPs and IPLVs for Non-Standard Centrifugal Chillers > 300 Tons


Centrifugal Chillers > 300 Tons
COPstd = 6.1
 


 

Condenser Flow Rate
 


 

2 gpm/ton
 

2.5 gpm/ton
 

3 gpm/ton
 

4 gpm/ton
 

5 gpm/ton
 

6 gpm/ton
 


Leaving Chilled Water Temperature (°F)
 

Entering Condenser Water Temperature (°F)
 

LIFTa
(°F)
 


Required COP and IPLV

 


46
 

75
 

29
 

6.80
 

7.11
 

7.35
 

7.71
 

7.97
 

8.16
 
45  
75   30   6.71   6.99   7.21   7.55   7.78   7.96  
44  
75   31   6.61   6.89   7.09   7.40   7.61   7.77  
43  
75   32   6.52   6.79   6.98   7.26   7.45   7.60  
42  
75   33   6.43   6.69   6.87   7.13   7.31   7.44  
41  
75   34   6.33   6.60   6.77   7.02   7.18   7.30  
46  
80   34   6.33   6.60   6.77   7.02   7.18   7.30  
40  
75   35   6.23   6.50   6.68   6.91   7.06   7.17  
45  
80   35   6.23   6.50   6.68   6.91   7.06   7.17  
44  
80   36   6.13   6.41   6.58   6.81   6.95   7.05  
43  
80   37   6.02   6.31   6.49   6.71   6.85   6.94  
42  
80   38   5.90   6.21   6.40   6.61   6.75   6.84  
41  
80   39   5.77   6.11   6.30   6.52   6.65   6.74  
46  
85   39   5.77   6.11   6.30   6.52   6.65   6.74  
40  
80   40   5.63   6.00   6.20   6.43   6.56   6.65  
45  
85   40   5.63   6.00   6.20   6.43   6.56   6.65  
44  
85   41   5.47   5.87   6.10   6.33   6.47   6.55  
43  
85   42   5.30   5.74   5.98   6.24   6.37   6.46  
42  
85   43   5.11   5.60   5.86   6.13   6.28   6.37  
41  
85   44   4.90   5.44   5.72   6.02   6.17   6.27  
40  
85   45   4.68   5.26   5.58   5.90   6.07   6.17  


Condenser DTb  

14.04
 

11.23
 

9.36
 

7.02
 

5.62
 

4.68
 



a    LIFT = Entering Condenser Water Temperature -- Leaving Chilled Water Temperature

b     Condenser DT = Leaving Condenser Water Temperature (F) - Entering Condenser Water Temperature (F)

Kadj = 6.1507 - 0.30244(X) + 0.0062692(X)2 - 0.000045595(X)3
where X = Condenser DT + LIFT

COPadj = Kadj * COPstd  


(Added by Ord. 94-75; Am. Ord. 01-47)




    
Article 11. Service Water Heating Systems
    and Equipment

Sections:
32-11.1    Scope.
32-11.2    General.
32-11.3    Basic requirements.

Sec. 32-11.1    Scope.
The requirements of this article apply to new water heating systems and equipment installed in new buildings, major additions to buildings or portions of buildings undergoing major alterations or repair. Emergency replacements of water heating equipment need not comply with this article. (Added by Ord. 94-75)

Sec. 32-11.2    General.
(a)    Information. Service water heating equipment shall be supplied with the information needed to make the analysis required to determine compliance with this code.
(b)    Compliance. The water heating system and equipment are in compliance with the requirements of this article when the basic requirements of Section 32-11.3 are satisfied.
(Added by Ord. 94-75)

Sec. 32-11.3    Basic requirements.
(a)    Sizing of Systems. Service water heating system design loads for the purpose of sizing and selecting systems shall be determined in accordance with the procedures described in Chapter 44 of ASHRAE Handbook, 1991 HVAC Applications, or a similar computation procedure. Table 11-2 may be used for sizing residential water heating systems.
(b)    Equipment Efficiency.
(1)    Minimum Equipment Efficiency.
(A)    All water heaters and hot water storage tanks shall meet the criteria of Table 11-1. Where multiple criteria are listed, all criteria shall be met. Where no criteria are provided, no requirements need be met.
(B)    Exception. Storage water heaters and hot water storage tanks having more than 140 gallons of storage capacity need not meet the standby loss (SL) or heat loss (HL) requirements of Table 11-1 if the tank surface area is thermally insulated to R-12.5 and if a standing pilot light is not used.
(2)    Data furnished by the equipment manufacturer or certified under a nationally recognized certification program or rating procedure shall be acceptable to satisfy these requirements.
(3)    Omissions. Omission of minimum performance requirements for certain classes of equipment does not preclude use of such equipment when appropriate.
(c)    Piping Insulation.
(1)    Circulating Systems and Systems with Pipes Heated by Heat Tape or Similar Means. Piping insulation shall conform to the requirements of Table 9-1 or an equivalent level as calculated in accordance with Equation 9-1.
(2)    Noncirculating Systems. The first eight feet of piping from a storage system that is maintained at a constant temperature shall be insulated as provided in Table 9-1 or to an equivalent level as calculated in accordance with Equation 9-1.
(d)    Temperature Controls.
(1)    Service water heating systems shall be equipped with temperature controls capable of adjusting storage temperatures from 90 degrees Fahrenheit to a temperature setting compatible with the intended use. Some representative hot water utilization temperatures are listed in the ASHRAE Handbook, 1991 HVAC Applications, Chapter 44, Table 3.
(2)    Exception. Service water heating systems serving residential dwelling units may be equipped with controls capable of adjustment down to 110 degrees Fahrenheit only.
(e)    Remote or Booster Heaters.
(1)    Where temperatures higher than 130 degrees Fahrenheit are required at certain outlets for a particular intended use, separate remote heaters or booster heaters shall be installed for those outlets.
(2)    Exception. Where it can be shown that either energy cost is not reduced by the application of this requirement or that the total installed cost of the equipment, maintenance and energy used over the life of the equipment is not reduced.
(f)    Circulating Hot Water Systems and Heated Pipes.
(1)    Systems designed to maintain temperatures in hot water pipes, including circulating hot water systems and heat tape on water pipes, shall be equipped with automatic time switches or other controls that can be set to turn off the system when availability of hot water is not required.
(2)    Exception. When the need for hot water is continuous.




Table 11-1 -- Minimum Performance of Water Heating Equipment


Category Type Fuel Input Rating Vol. Input to Test Energy Et g Standby
Vol. Ratio Method Factor c % Loss d
(Btuh/gal) %/hr

NAECA    all    electricf    <12kW     all         DOE Test     >0.93-0.00132V
Covered    storage    gas    <75,000 Btuh     all         Proc. 10     >0.62-0.0019V
Water    instantaneous    gas    <200,000 Btuh all        CFR, Part     >0.62-0.0019V
Heating    storage    oil    <105,000 Btuh all        430     >0.59-0.0019V
Equipmenta    instantaneous    oil    <210,000 Btuh all             >0.59-0.0019V

pool heater    gas/oil    all     all         ANSI         >78%
    Z21.56-1989

Other Water    storage    electric    all     all         ANSI                 <0.30+27/VT
Heating                         Z21.10.3,
Equipmentb    storage/    gas/oil    <155,000 Btuh all <4,000     1990         >78%     <1.3+114/VT
instantaneous        >155,000 Btuh all <4,000             >78%     <1.3+95/VT
<10 >4,000             >80%     -
e 10 >4,000             >77%     <2.3+67/VT

air-source    electric    >24A     all                 >3.0
heat pumph

Unfired                 all                         <6.5Btuh/ft2e
Storage
Tanks

a.    Consistent with National Appliance Energy Conservation Act (NAECA) of 1987.

b.    All except those water heaters covered by NAECA.

c.    V is the rated storage volume as specified by the manufacturer.

d.    VT is the storage volume in gallons as measured during the test to determine the standby loss. VT may differ from V, but it is within the tolerances allowed by the applicable Z21 and UL standards. Accordingly, for the purpose of estimating the standby loss requirement using the rated volume shown on the rating plate VT should be considered as no less than 0.95V for gas and oil water heaters and no less than 0.90V for electric water heaters.

e.    Heat loss of tank surface area (Btuh/ft2) based on 80°F water-air temperature difference.

f.    Electric water heaters covered by NAECA include heat pumps with maximum current ratings of 24 A at a voltage no greater than 250 V.

g.    Et = thermal efficiency. C.O.P. for heat pumps.

h.    Heat pump C.O.P. minimum requirements based on 75°F DB, 63°F WB, 70°F inlet and 130°F leaving water temperature (heat pumps rated for a maximum leaving water temperature of 120°F shall have a minimum C.O.P. of 3.7).



(g)    Swimming Pools, Hot Tubs and Spas.
(1)    Swimming Pool, Hot Tub and Spa Heaters. All water heaters for swimming pools, hot tubs and spas shall meet the criteria of Table 11-1 and shall be equipped with a readily accessible switch to allow shutting off the heater without adjusting the thermostat setting and to allow restarting without manually relighting a pilot light.
(2)    Pool Heating Systems.
(A)    Active solar or heat pump heating systems shall be used for swimming pool heating.
(B)    Exception. Alternative systems may be used if it can be shown that they are more cost-effective as determined by life-cycle cost analysis as performed in accordance with procedures defined by the National Institute of Standards and Technology (NIST) Life-Cycle Costing Manual for the Federal Energy Management Program, NIST Handbook 135, and its supplement, Energy Price Indices and Discount Factors for Life-Cycle Cost Analysis. Assumptions used in any calculation should use the latest price indices and discount factors available at the time the calculation is submitted to the city.
(3)    Time Switches.
(A)    Time switches shall be installed so that the pump can be set to run in the off-peak electric demand period and can be set for the minimum time necessary to maintain the water in a clear and sanitary condition in keeping with applicable health standards.
(B)    Exception. Pumps required to operate solar or waste-heat recovery pool heating systems need not use time switches.



Table 11-2 -- Residential Hot Water Consumption for Sizing
Water Heating Systems



Residential                        Hot Water
Dwelling                        Consumption
Unit Size (ft 2 ) a                          (gal/day)

< 1,000                         30
> 1,000 and < 1,400                     40
> 1,400 and < 1,800                     60
> 1,800                         80

a Excluding garage area.

(h)    Heat Traps. Vertical pipe risers serving storage water heaters and storage tanks not having integral heat traps and serving a nonrecirculating system shall have heat traps on both the inlet and outlet piping as close as practical to the storage tank. A heat trap is a means to counteract the natural convection of heated water in a vertical pipe run. The means is either a device specifically designed for the purpose or an arrangement of tubing that forms a loop of 360 degrees or piping that from the point of connection to the water heater (inlet or outlet) includes a length of piping directed downwards before connection to the vertical piping of the supply water or hot water distribution system, as applicable.
(Added by Ord. 94-75; Am. Ord. 01-47)


     Article 12. Energy Management

Sections:
32-12.1    General
32-12.2    Other specific control requirements.
32-12.3    General requirements.

Sec. 32-12.1    General.
This article describes the minimum measurement, control, testing and documentation features that shall be provided for the building. The intent is to provide design data along with a means of testing the facility in its completed form so that the facility can be operated in an energy-efficient manner as intended by this code. (Added by Ord. 94-75)

Sec. 32-12.2    Other specific control requirements.
See the following articles for specific control requirements for specific systems and equipment:
Article 5 - electric power and distribution systems
Article 6 - lighting systems
Article 9 - HVAC systems
Article 10 - HVAC equipment
Article 11 - service water heating systems and equipment
(Added by Ord. 94-75)

Sec. 32-12.3    General requirements.
(a)    Public Utility Meter. Each public utility energy service meter provided shall be located or arranged so that the meter can be monitored. Monitoring of utility company meters and the installation of submetering or checkmetering shall be in compliance with the utility company regulations.
(b)    Building Energy Measurement System.
(1)    Each distinct building energy service shall have a measurement system provided to accumulate a record or indicator reading of the overall amounts of the energy being delivered.
(2)    Exception. A building of 5,000 ft2 gross floor area or less in a complex of buildings may have its measurement system included with another building in the same complex.
(c)    Equipment Energy Measurement. All equipment used for heating or cooling and HVAC delivery systems of greater than 20 kVA or 60,000 Btu/h energy input shall be arranged so that the inputs and outputs such as flow, temperature and pressure can be individually measured to determine the equipment energy consumption, the installed performance capabilities and efficiencies, or both. The intent of this requirement is to provide physical access or other provisions in the equipment or layout that will allow these measurements in the future if so desired. Installation of the measurement equipment is not required for compliance with this code.
(Added by Ord. 94-75)


     Article 13. Building Energy Cost Budget Method

Sections:
32-13.1    Purpose.
32-13.2    Scope.
32-13.3    General
32-13.4    Determination of the annual energy cost budget.
32-13.5    Design energy consumption (DECON) and design energy cost (DECOS).
32-13.6    Compliance.
32-13.7    Standard calculation procedure.
32-13.8    The simulation tool.


Sec. 32-13.1    Purpose.
This article provides criteria for the design of energy- efficient buildings that allow greater design flexibility than the other compliance paths of this code, while providing building energy efficiency levels consistent with the other paths. This path provides an opportunity for the building designer to evaluate and take credit for innovative energy efficiency designs, materials, and equipment such as daylighting, heat recovery, better zonal temperature control, and thermal storage, as well as other applications of "off peak" electrical energy that cannot be accounted for in the prescriptive or system performance paths. Designers are encouraged to employ the building energy cost budget method set forth in this article for evaluating proposed design alternatives in preference to using the prescriptive or system performance methods. (Added by Ord. 94-75)

Sec. 32-13.2    Scope.
The building energy cost budget method may be used when designs fail to meet either the prescriptive or system performance criteria of this code. It may be employed for evaluating the compliance of all proposed designs (except shell buildings). (Added by Ord. 94-75)

Sec. 32-13.3    General.
Compliance is achieved when the estimated design energy cost (DECOS) is not greater than the energy cost budget (ECB). (Added by Ord. 94-75)

Sec. 32-13.4    Determination of the annual energy cost budget.
The energy cost budget (ECB) is the summation of the 12 monthly energy cost budgets (ECBm). Each ECBm is the product of the monthly budget energy consumption (BECONm) of each type of energy used multiplied by that monthly energy cost (ECOSm) per unit of energy for each type of energy used. The ECB shall be determined in accordance with Equation 13-1 as follows:


Equation 13-1

ECB = ECBjan + ...ECBm + ... + ECBdec


Based on Equation l3-2:

Equation 13-2

ECBm = (BECONm1) x (ECOSm1) + .. + (BECONmi) x (ECOSmi)



where:

ECB        = The annual Energy Cost Budget

ECBm        = The monthly Energy Cost Budget

BECONmi    = The monthly Budget Energy Consumption of the ith type of energy

ECOSmi        = The monthly Energy Cost, per unit of the ith type of energy

The ECOSmi shall be determined using current rate schedules or contract prices available at the building site for all types of energy purchased. These costs shall include demand charges, rate blocks, time of use rates, interruptable service rates, delivery charges, fuel adjustment factors, taxes, and all other charges applicable for the type, location, operation, and size of the proposed building. The BECONmi shall be calculated from the first day through the last day of each month, inclusive.
(a)    Reference Building. Each floor shall be oriented exactly as in the proposed design. The form, gross and conditioned floor area of each floor and the number of floors shall be as in the proposed design. All other characteristics such as lighting, envelope and HVAC system shall meet the requirements of Articles 5 through 12.
(b)    Calculation Procedure and Simulation Tool. The reference building shall be modeled using the criteria of Sections 32-13.7 and 32-13.8. The modeling shall use a climate data set appropriate for both the site and the complexity of the energy conserving features of the design. ASHRAE WYEC weather tapes or bin weather data shall be a default choice.
(Added by Ord. 94-75)

Sec. 32-13.5    Design energy consumption (DECON) and design energy cost (DECOS).

The DECON shall be calculated by modeling the proposed design using the same methods, assumptions, climate data, and simulation tool as were used to establish the ECB, except as explicitly provided in Section 32-13.7. The DECOS shall be calculated as provided in Equation 13-3 using the same rate schedules or contract prices as were used to establish the ECB. If the proposed design includes cogeneration or renewable energy sources designed for the sale of energy off site, the energy cost and income resulting from outside sales shall not be included in the calculation of DECOS. Such systems shall be modeled as operating to supply energy needs of the proposed design only.


Equation 13-3

DECOS = DECOSjan + ...DECOSm .... + DECOSdec


Based on Equation 13-4:


Equation 13-4


DECOSm = (DECONm1) x (ECOSm1) + ...+ (DECONmi) x (ECOSmi)

where:

DECOS        = The annual Design Energy Cost

DECOSm    = The monthly Design Energy Cost

DECONmi    = The monthly Design Energy Consumption of the ith type of energy

ECOSmi        = The monthly Energy Cost per unit of the ith type     of energy (See Section 32-13.4 for ECOSmi     definitions)

The DECONmi shall be calculated from the first day through the last day of the month, inclusive.
(Added by Ord. 94-75)

Sec. 32-13.6    Compliance.
The proposed design complies with this code when the design energy cost (DECOS) is not greater than the energy cost budget (ECB) as provided in Equation 13-5, and all of the basic requirements of Sections 32-5.3, 32-6.3, 32-8.3, 32-9.3, 32-10.3, 32-11.3, and 32-12.3 are met.


Equation 13-5

DECOS < ECB


(Added by Ord. 94-75)

Sec. 32-13.7    Standard calculation procedure.
The standard calculation procedure consists of methods and assumptions for calculating the ECB for the reference building and the DECON and DECOS of the proposed design. In order to maintain consistency between the ECB and the DECOS, the input assumptions in this section shall be used.


"Prescribed" assumptions shall be used without variation. "Default" assumptions shall be used unless the designer can demonstrate that a different assumption better characterizes the building's use over its expected life. Any modification of a default assumption shall be used in modeling both the reference building and the proposed design unless the designer demonstrates a clear cause to do otherwise. Special procedures necessary for speculative buildings are discussed in subsection (g).
(a)    Orientation and Shape. The reference building shall consist of the same number of stories and gross floor area for each story as the proposed design. Each floor shall be oriented exactly as the proposed design. The geometric form shall be the same as the proposed design. Glass area and orientation shall be exactly as the proposed design.
(b)    Internal Loads. Internal loads shall be modeled as noted in the following subdivisions (1) through (3).
(1)    Occupancy. Occupancy schedules shall be default assumptions. The same assumptions shall be made in computing design energy consumption as are used in calculating the energy cost budget.
Occupancy levels vary by building type and time of day. Table 13-1, Occupancy Density, establishes the density presented as ft
2/person of conditioned floor area that will be used by each building type. Table 13-5, Building Schedule Percentage Multipliers, establishes the percentage of the people that are in the building by hours of the day for each building type.
(2)    Lighting. Interior lighting power allowance (ILPA), for calculating the ECB shall be determined from Article 6. The lighting power used to calculate the DECOS shall be the actual adjusted power of the proposed lighting design. If the lighting controls in the proposed design are more effective at saving energy than those required by Section 32-6.3, the actual installed lighting power shall be used along with the schedules reflecting the action of the controls to calculate the DECOS. This "actual installed lighting power" shall not be adjusted by the power adjustment factors listed in Table 6-4.
Lighting levels in buildings vary based on the type of uses within buildings, by area and by time of day. Table 13-5 contains the lighting energy profiles which establish the percentage of the lighting load that is ON in each reference building by hour of the day. These profiles are default assumptions and can be changed if required when calculating the ECB to provide, for example, a 12-hour rather than an eight-hour workday.
(3)    Receptacle. Receptacle loads and profiles are default assumptions. The same assumptions shall be made in calculating design energy consumption as were used in calculating the energy cost budget.
Receptacle loads include all general service loads that are typical in a building. These loads should include additional process electrical usage, but exclude HVAC primary or auxiliary electrical usage. Table 13-2, Receptacle Power Densities, establishes the density in W/ft2 to be used. The receptacle energy profiles shall be the same as the lighting energy profiles in Table 13-5. This profile establishes the percentage of the receptacle load that is ON by hour of the day and by building type.
(c)    Envelope.
(1)    Insulation and Glazing. The insulation and glazing characteristics of the reference building envelope shall be determined from Section 32-8.4. In the calculation of the DECON of the proposed design, the envelope characteristics of the proposed design shall be used. The reference building shall not have an overhang. The reference building shall be modeled with a glazing material with a constant shading coefficient equal to the relative solar heat gain requirements in Section 32-8.4(c).
(2)    Infiltration.
(A)    For reference buildings, infiltration assumptions shall use the prescribed assumptions for calculating the ECB and default assumptions for the DECON. Infiltration shall impact only perimeter zones. When the HVAC system is ON, no infiltration shall be assumed to occur. When the HVAC system is OFF, the infiltration rate for buildings with or without operable windows shall be assumed to be 0.038 cfm/ft2 of the gross exterior wall.
(B)    Exception. Hotels/motels and residential buildings shall have infiltration rates of 0.038 cfm/ft2 of gross exterior wall area at all times.
(3)    Envelope and Ground Absorptivities. Absorptivity assumptions shall be prescribed assumptions for the reference building and default assumptions for the proposed design. The solar absorptivity of opaque elements of the building envelope shall be assumed to be 70 percent. The solar absorptivity of ground surfaces shall be assumed to be 80 percent (20 percent reflectivity).
(4)    Window Management. If the plans and specifications show interior shading devices which perform better than a medium-colored venetian blind, then those shading devices may be modeled in the proposed design, and the reference building shall be modeled with medium-colored venetian blinds. Otherwise, interior shading shall be modeled identically in the proposed and reference buildings, either with medium-colored venetian blinds or without interior shades.
If the simulation tool has a window management algorithm, then manually operated shades shall be assumed to close when solar gain exceeds 30 Btu/h-ft2. Otherwise, assume that half the blinds are closed continuously. If the proposed design includes special controls for interior shading devices, then they may be modeled, and the blinds in the reference building shall be assumed to close when solar gain exceeds 30 Btu/h-ft2.
(5)    Shading. For reference buildings and the proposed design, shading by permanent structures, terrain, and vegetation may be taken into account for computing energy consumption, whether or not these features are located on the building site. A permanent fixture is one that is likely to remain for the life of the proposed design.
(d)    HVAC Systems and Equipment. The HVAC system and equipment type in the reference building shall be the same as the proposed design, but the system and equipment in the reference building shall exactly meet the requirements of Articles 9 and 10. Special energy cost-reducing features of the proposed design need not be included in the reference building if they are not required in Articles 9 and 10. If the HVAC system type in the proposed design is not allowed under the requirements of Section 32-9.4, then a reasonably similar complying system shall be modeled in the reference building.
(1)    HVAC Zones. For multi-family buildings, the reference building shall have one zone per dwelling unit. The proposed design shall have one zone per unit unless zonal thermostatic controls are provided within units; in this case, two zones per unit shall be modeled.
In all other building types, HVAC zones for calculating the ECB and the DECOS shall be exactly the same. The zones in the simulation shall correspond to the zones provided by the controls in the proposed design.
Building types such as assembly or warehouse may be modeled as a single zone if there is only one space.
Thermally similar zones, such as those facing one orientation on different floors, may be grouped together for the purposes of either the DECOS or ECB simulation.
(2)    Equipment Sizing and Redundant Equipment. Process loads should be modeled in calculating both the ECB and the DECOS. If process loads are modeled, the equipment shall be sized in accordance with the methods of Article 9 to include the capacity to meet the process loads. The designer shall document the installation of process equipment and the size of process loads.
If process loads are not modeled, then for calculating the ECB of reference buildings HVAC equipment shall be sized to meet the requirements of Section 32-9.4(a) without utilizing any of the exceptions.
For calculating the DECOS, actual air flow rates and installed equipment size shall be used in the simulation, except that excess capacity provided to meet process loads need not be modeled if the process load was not modeled in setting the ECB. Equipment sizing in the simulation of the proposed design shall correspond to the equipment actually selected for the design, and the designer shall not use equipment sized automatically by the simulation tool.
Redundant and/or emergency equipment need not be simulated if it is controlled such that it will not be operated during normal operations of the building.
(e)    Service Water Heating. The service water heating loads for reference buildings are defined in terms of Btu/person-hours in Table 13-3. The service water heating loads from Table 13-3 are prescribed for multi-family buildings and default for all other buildings. The same service water heating load assumptions shall be made in calculating DECOS as were used in calculating the ECB.
The service water heating system, including piping losses, for the reference building shall be modeled using the methods of the ASHRAE Handbook, 1991 HVAC Applications, using a system that meets all requirements of Article 11.
The service water heating equipment type for the reference building shall be an electric resistance storage water heater if the proposed building uses electric water heating or shall be a utility gas storage water heater if the proposed building uses gas water heating.
(f)    Controls.
(1)    Conditioned and Unconditioned Spaces.
(A)    All occupied spaces in the reference and proposed buildings shall be simulated as being air- conditioned. When no cooling system is shown on the plans for the proposed design, reasonable assumptions shall be made about the HVAC system type, and the same assumptions shall be made for the proposed and reference buildings.
(B)    Exception. Unconditioned spaces which meet the envelope requirements of Sections 32-8.4 or 32-8.5 may be omitted from the thermal model in the proposed and reference designs.
(2)    Space Temperature Controls.
(A)    Space temperature controls for the reference building except multi-family shall be set at 75 degrees Fahrenheit for space cooling. The system shall be OFF during off-hours according to the appropriate schedule in Table 13-3.
(B)    Exceptions. Setback shall not be modeled in determining either the ECB or DECOS if setback is not realistic for the proposed design such as a facility being operated 24 hours per day.
(3)    For multi-family buildings, the thermostat schedule for the dwelling units shall be as in Table 13-4. The reference building shall use the single zone schedule. The proposed design shall use the two-zone schedule only if zonal thermostatic controls are provided. The thermostat assumptions for multi-family buildings are prescribed assumptions.
(4)    When providing for outdoor air ventilation when calculating the ECB, controls shall be assumed to close the outside air intake to reduce the flow of outside air to zero cfm during "setback" and "unoccupied" periods. Ventilation using inside air may still be required to maintain scheduled setback temperature. Outside air ventilation, during occupied periods, shall be as required by ASHRAE Standard 62-1989 or the proposed design, whichever is greater.
(5)    If dehumidification requires subcooling of supply air, then reheat for the reference building shall be from recovered waste heat such as condenser waste heat.
(g)    Speculative Buildings.
(1)    Lighting. The interior lighting power allowance (ILPA) for calculating the ECB shall be determined from Table 6-5. The DECOS may be based on an assumed adjusted lighting power for future lighting improvements.
The assumption about future lighting power used to calculate the DECOS shall be documented so that the future installed lighting systems may be in compliance with this assumption. Documentation shall be provided to enable future lighting systems to use either the prescriptive method of Section 32-6.4 or the systems performance method of Section 32-6.5. Documentation for future lighting systems that use the prescriptive method of Section 32-6.4 shall be stated as a maximum adjusted lighting power for the tenant spaces. The adjusted lighting power allowance for tenant spaces shall account for the lighting power provided for the common areas of the building.
Documentation for future lighting systems that use the systems performance method of Section 32-6.5 shall be stated as a required lighting adjustment. The required lighting adjustment is the whole building lighting power assumed in order to calculate the DECOS minus the ILPA value from Table 6-5 that was used to calculate the ECB. When the required lighting adjustment is less than zero, a complete lighting design shall be developed for one or more representative tenant spaces, demonstrating acceptable lighting within the limits of the assumed lighting power limit.
(2)    HVAC Systems and Equipment. If the HVAC system is not completely specified in the plans, the DECOS shall be based on reasonable assumptions about the construction of future HVAC systems and equipment. These assumptions shall be documented so that future HVAC systems and equipment may be in compliance with this assumption.
(Added by Ord. 94-75)

Sec. 32-13.8    The simulation tool.
(a)    Annual energy consumption should be simulated with a multizone, 8,760 hours per year building energy program. The tool should account for:
(1)    The dynamic heat transfer of the building envelope, including the effects of solar and internal gains;
(2)    Equipment efficiencies as a function of load and climate;
(3)    Lighting and HVAC system controls and distribution systems by simulating the whole building;
(4)    The operating schedule of the building including night setback during various times of the year;
(5)    Energy consumption information at a level necessary to determine the ECB and DECOS via the appropriate utility rate schedules.
(b)    While analysis tools should simulate an entire year on an hour-by-hour basis (8,760 hours per year), tools that approximate this dynamic analysis procedure or provide equivalent results are acceptable.
(Added by Ord. 94-75)




Table 13-1 -- Occupancy Density


Conditioned Floor Area
Building Type     Sq ft/Person

1. Assembly     50
2. Office     275
3. Retail     300
4. Warehouse    15,000
5. School     75
6. Hotel/Motel     250
7. Restaurant     100
8. Health/Institutional     200
9. Multi-family     0a
10. Light Manufacturing     750

Heat generation: Btu/person-hour: 230 sensible and 190 latent

a. See notes for multi-family high-rise in Table 13-5.


Table 13-2 -- Receptacle Power Densities


Building Type Watts/ft 2 of
Conditioned Floor Area

1. Assembly    0.25
2. Office    0.75
3. Retail    0.25
4. Warehouse    0.1
5. School    0.5
6. Hotel/Motel    0.25
7. Restaurant    0.1
8. Health    1.0
9. Multi-family    0a
10. Light Manufacturing    0.2b

a.    See notes for multi-family high-rise in Table 13-5.
b.    Non-process load.





Table 13-3 -- Service Hot Water Quantities


Building Type Btu/Person-hour a

1. Assembly     215
2. Office     175
3. Retail     135
4. Warehouse     225
5. School     215
6. Hotel/Motel    1,110
7. Restaurant     390
8. Health     135
9. Multi-family    1,700b
10. Light Manufacturing     225c

a.    This value is the number to be multiplied by the percentage multipliers of the building profile schedules in Table 13-5. See Table 13-1 for occupancy levels.
b.    Total hot water use per dwelling unit for each hour shall be 3,400 Btu/h times the multi-family Service Water Heating (SWH) system multiplier from Table 13-5.
c.    Non-process load.




Table 13-4 -- Building Cooling Thermostat Setpoint Schedule

     Hour of Day

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Assembly
Weekday    OFF    OFF    OFF    OFF    OFF     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75    OFF
Weekend    OFF    OFF    OFF    OFF    OFF    OFF     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75    OFF

Office
Weekday    OFF    OFF    OFF    OFF    OFF    OFF     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75    OFF    OFF
Sat.    OFF    OFF    OFF    OFF    OFF    OFF     75     75     75     75     75     75     75     75     75     75     75     75    OFF    OFF    OFF    OFF    OFF    OFF
Sun.    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF

Retail
Weekday    OFF    OFF    OFF    OFF    OFF    OFF     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75    OFF    OFF    OFF
Sat.    OFF    OFF    OFF    OFF    OFF    OFF     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75    OFF    OFF
Sun.    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF     75     75     75     75     75     75     75     75     75    OFF    OFF    OFF    OFF    OFF    OFF    OFF

Warehouse
Weekday    OFF    OFF    OFF    OFF    OFF    OFF    OFF     75     75     75     75     75     75     75     75     75     75    OFF    OFF    OFF    OFF    OFF    OFF    OFF
Sat.    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF     75     75     75     75     75     75     75     75    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF
Sun.    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF

School
Weekday    OFF    OFF    OFF    OFF    OFF    OFF    OFF     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75    OFF    OFF
Sat.    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF     75     75     75     75     75    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF
Sun.    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF

Hotel
All Days     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75

Restaurant
Weekday     75     75     75    OFF    OFF    OFF    OFF     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75
Sat.     75     75     75    OFF    OFF    OFF    OFF    OFF    OFF     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75
Sun.     75     75     75    OFF    OFF    OFF    OFF    OFF    OFF    OFF     75     75     75     75     75     75     75     75     75     75     75     75     75     75

Health
All Days     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75


Multi-family
One-Zone
All Days     78     78     78     78     78     78     78     78     78     78     78     78     78     78     78     78     78     78     78     78     78     78     78     78

Two-Zone
Bedrooms
& Bathrooms
All Days     78     78     78     78     78     78     78     78     78     85     85     85     85     85     85     85     85     78     78     78     78     78     78     78
Other Rooms
All Days     85     85     85     85     85     85     78     78     78     78     78     78     78     78     78     78     78     78     78     78     78     78     78     78

Light Manufacturing
Weekday    OFF    OFF    OFF    OFF    OFF    OFF     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75     75    OFF    OFF
Sat.    OFF    OFF    OFF    OFF    OFF    OFF     75     75     75     75     75     75     75     75     75     75     75     75    OFF    OFF    OFF    OFF    OFF    OFF
Sun.    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF




Table 13-5 -- Building Schedule Percentage Multipliers a,b,c

    Hour of Day

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Assembly

Occupancy
Weekday     0     0     0     0     0     0     0     0     20     20     20     80     80     80     80     80     80     80     20     20     20     20     10     0
Sat     0     0     0     0     0     0     0     0     20     20     20     60     60     60     60     60     60     60     60     60     60     80     10     0
Sun     0     0     0     0     0     0     0     0     10     10     10     10     10     70     70     70     70     70     70     70     70     70     20     0

Lighting
Weekday     0     0     0     0     0     0     40     40     40     75     75     75     75     75     75     75     75     75     75     75     75     75     25     0
Sat     0     0     0     0     0     0     0     30     30     50     50     50     50     50     50     50     50     50     50     50     50     50     0     0
Sun     0     0     0     0     0     0     0     30     30     30     30     30     65     65     65     65     65     65     65     65     65     65     0     0

HVAC
Weekday    OFF    OFF    OFF    OFF    OFF    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    OFF
Sat    OFF    OFF    OFF    OFF    OFF    OFF    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    OFF
Sun    OFF    OFF    OFF    OFF    OFF    OFF    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    OFF

Service Hot Water
Weekday     0     0     0     0     0     0     0     0     0     5     5     35     5     5     5     5     5     0     0     0     0     0     0     0
Sat     0     0     0     0     0     0     0     0     0     5     5     20     0     0     0     0     0     0     0     65     30     0     0     0
Sun     0     0     0     0     0     0     0     0     0     5     5     10     0     0     0     0     0     0     0     65     30     0     0     0

Office

Occupancy
Weekday     0     0     0     0     0     0     0     10     20     95     95     45     45     95     95     95     95     95     30     10     10     10      0     0
Sat     0     0     0     0     0     0     0     10     10     30     30     30     30     10     10     10     10     10     0     0     0     0     0     0
Sun     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0

Lighting
Weekday     0     0     0     0     0     0     10     30     90     90     90     90     80     90     90     90     90     90     30     30     20     20     0     0
Sat     0     0     0     0     0     0     10     10     30     30     30     30     15     15     15     15     15     15     0     0     0     0     0     0
Sun     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0

HVAC
Weekday    OFF    OFF    OFF    OFF    OFF    OFF    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    OFF    OFF


Sat    OFF    OFF    OFF    OFF    OFF    OFF    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    OFF    OFF    OFF    OFF    OFF    OFF
Sun    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF

Service Hot Water
Weekday     0     0     0     0     0     0     0     15     30     35     35     45     55     50     30     30     40     20     20     10     15     5     0     0
Sat     0     0     0     0     0     0     0     10     10     20     15     20     15     15     10     10     10     0     0     0     0     0     0     0
Sun     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0

Retail

Occupancy
Weekday     0     0     0     0     0     0     0     10     20     50     50     70     70     70     70     80     70     50     50     30     30     0     0     0
Sat     0     0     0     0     0     0     0     10     20     50     60     80     80     80     80     80     80     60     20     20     20     10     0     0
Sun     0     0     0     0     0     0     0     0     0     10     20     20     40     40     40     40     40     20     10     0     0     0     0     0

Lighting
Weekday     0     0     0     0     0     0     0     20     50     90     90     90     90     90     90     90     90     90     60     60     50     0     0     0
Sat     0     0     0     0     0     0     0     10     30     60     90     90     90     90     90     90     90     90     50     30     30     10     0     0
Sun     0     0     0     0     0     0     0     0     0     10     40     40     60     60     60     60     60     40     20     0     0     0     0     0

HVAC
Weekday    OFF    OFF    OFF    OFF    OFF    OFF    ON    ON    ON    ON    ON     ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    OFF    OFF    OFF
Sat    OFF    OFF    OFF    OFF    OFF    OFF    ON    ON    ON    ON    ON    ON     ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    OFF    OFF
Sun    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    ON    ON    ON    ON     ON    ON    ON    ON    ON    ON    ON    OFF    OFF    OFF    OFF    OFF

Service Hot Water
Weekday     0     0     0     0     0     0     0     10     20     30     40     55     60     60     45     40     45     45     40     30     30     0     0     0
Sat     0     0     0     0     0     0     0     15     20     25     40     50     55     55     45     45     45     45     40     35     25     20     0     0
Sun     0     0     0     0     0     0     0     0     0     10     25     30     35     35     30     30     35     30     20     0     0     0     0     0




Table 13-5 -- Building Schedule Percentage Multipliers
(continued)

Hour of Day


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Warehouse

Occupancy
Weekday     0     0     0     0     0     0     0     15     70     90     90     90     50     85     85     85     20     0     0     0     0     0     0     0
Sat     0     0     0     0     0     0     0     0     20     20     20     20     10     10     10     10     0     0     0     0     0     0     0     0
Sun     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0

Lighting
Weekday     0     0     0     0     0     0     0     40     70     90     90     90     90     90     90     90     90     0     0     0     0     0     0     0
Sat     0     0     0     0     0     0     0     0     10     25     25     25     10     10     10     10     0     0     0     0     0     0     0     0
Sun     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0      0

HVAC
Weekday    OFF    OFF    OFF    OFF    OFF    OFF    OFF    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    OFF    OFF    OFF    OFF    OFF    OFF    OFF
Sat    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    ON    ON    ON    ON    ON    ON    ON    ON    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF
Sun    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF

Service Hot Water
Weekday     0     0     0     0     0     0      0     5     25     35     35     45     55     40     35     40     15     0     0     0     0     0     0     0
Sat     0     0     0     0     0     0     0     0     0     10     10     15     0     0     0     0     0     0     0     0     0     0     0     0
Sun     0     0      0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0      0

School

Occupancy
Weekday     0     0     0     0     0     0     0     5     75     90     90     80     80     80     80     45     15     5     15     20     20     10     0     0
Sat     0     0     0     0     0     0     0     0     10     10     10     10     10     0     0     0     0     0     0     0     0     0     0     0
Sun     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0

Lighting
Weekday     0     0     0     0     0     0     0     30     85     95     95     95     80     80     80      70     50     50     35     35     35     30     0     0
Sat     0     0     0     0     0     0     0     0     15     15     15     15     15     0     0     0     0     0     0     0     0     0     0     0


Sun     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0

HVAC
Weekday    OFF    OFF    OFF    OFF    OFF    OFF    OFF    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    OFF    OFF
Sat    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    ON    ON    ON    ON    ON    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF
Sun    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF    OFF

Service Hot Water
Weekday     0     0     0     0     0     0     0     5     30     55     60     70     75     80     60     60     5     5     15     20     20     20     0     0
Sat     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0
Sun     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0     0      0

Hotel

Occupancy
Weekday     90     90     90     90     90     90     70     40     40     20     20     20     20     20     20     30     50     50     50     70     70     80     90     90
Sat     90     90     90     90     90     90     70     50     50     30     30     30     30     30     30     30     30     50     60     60     60     70     70     70
Sun     70     70     70     70     70     70     70     70     50     50     50     30     30     20     20     20     30     40     40     60     60     80     80     80

Lighting
Weekday     20     15     10     10     10     20     40     50     40     40     25     25     25     25     25     25     25     25     60     80     90     80     60     30
Sat     20     20     10     10     10     10     30     30     40     40     30     25     25     25     25     25     25     25     60     70     70     70     60     30
Sun     30     30     20     20     20     20     30     40     40     30     30     30     30     20     20     20     20     20     50     70     80     60     50     30

HVAC
Weekday    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON
Sat    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON
Sun    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON

Service Hot Water
Weekday     20     15     15     15     20     25     50     60     55     45     40     45     40     35     30     30     30     40     55     60     50     55     45     25
Sat     20     15     15     15     20     25     40     50     50     50     45     50     50     45     40     40     35     40     55     55     50     55     40     30
Sun     25     20     20     20     20     30     50     50     50     55     50     50     40     40     30     30     30     40     50     50     40     50     40     20




Table 13-5 -- Building Schedule Percentage Multipliers
(continued)


     Hour of Day

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Restaurant

Occupancy
Weekday     15     15     5     0     0     0     0     5     5     5     20     50     80     70     40     20     25     50     80     80     80     50     35     20
Sat     30     25     5     0     0     0     0     0     0     5     20     45     50     50     35     30     30     30     70     90     70     65     55     35
Sun     20     20     5     0     0     0     0     0     0     0     10     20     25     25     15     20     25     35     55     65     70     35     20     20

Lighting
Weekday     15     15     15     15     15     20     40     40     60     60     90     90     90     90     90     90     90     90     90     90     90     90     50     30
Sat     20     15     15     15     15     15     30     30     60     60     80     80     80     80     80     80     80     90     90     90     90     90     50     30
Sun     20     15     15     15     15     15     30     30     50     50     70     70     70     70     70     70     60     60     60     60     60     60     50     30

HVAC
Weekday    ON    ON    ON    OFF    OFF    OFF    OFF    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON
Sat    ON    ON    ON    OFF    OFF    OFF    OFF    OFF    OFF    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON
Sun    ON    ON    ON    OFF    OFF    OFF    OFF    OFF    OFF    OFF    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON

Service Hot Water
Weekday     20     15     15     0     0     0     0     60     55     45     40     45     40     35     30     30     30     40     55     60     50     55     45     25
Sat     20     15     15     0     0     0     0     0     0     50     45     50     50     45     40     40     35     40     55     55     50     55     40     30
Sun     25     20     20     0     0     0     0     0     0     0     50     50     40     40     30     30     30     40     50     50     40     50     40     20

Health

Occupancy
Weekday     0     0     0     0     0     0     0     10     50     80     80     80     80     80     80     80     80     50     30     30     20     20     0     0
Sat     0     0     0     0     0     0     0     10     30     40     40     40     40     40     40     40     40     10     10     0     0     0     0     0
Sun     0     0     0     0     0     0     0     0     5     5     5     5     5     5     5     5     0     0     0     0     0     0     0     0

Lighting
Weekday     0     0     0     0     0     0     0     50     90     90     90     90     90     90     90     90     90     30     30     30     30     30     0     0
Sat     0     0     0     0     0     0     0     20     40     40     40     40     40     40     40     40     40     40     10     0     0     0     0     0
Sun     0     0     0     0     0     0     0     0     10     10     10     10     10     10     10     10     0     0     0     0     0     0     0     0


HVAC
Weekday    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON
Sat    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON
Sun    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON

Service Hot Water
Weekday     0     0     0     0     0     0     0     15     55     65     75     80     70     80     75     70     60     40     15     15     15     5     0     0
Sat     0     0     0     0     0     0     0     0     15     25     25     25     20     20     20     20     20     5     0     0     0     0     0     0
Sun     0     0     0     0     0     0     0     0     0     15     15     15     15     15     15     0     0     0     0     0     0     0     0     0



Table 13-5 -- Building Schedule Percentage Multipliers
(continued)


     Hour of Day

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24


Multi-Family

Service Hot Water
Weekday     0     0     0     5     5     5     80     70     50     40     20     20     25     25     50     50     70     70     35     20     15     15     5     0
Sat     0     0     0     0     0     0     20     45     50     50     35     30     30     30     70     90     70     65     55     35     30     25     5     0
Sun     0     0     0     0     0     0     0     20     25     25     15     20     25     35     55     65     70     35     20     20     20     20     5     0

HVAC Systems
Weekday    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON
Sat    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON
Sun    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON    ON

One-zone Dwelling Unit

Occupancyd
All Days     67     67     67     67     67     67     67     49     21     21     21     21     21     21     21     21     21     67     67     67     67     67     67     67
Lightinge
All Days     0     0     0     0     0     0     95     85     0     0     0     0     0     0     0     0     0     0     0     90     90     90     90     90
Equipmentf
All Days     22     22     22     22     22     22     36     76     34     36     36     64     64     36     36     36     36     87     97     43     43     43     31     31

Two-zone Dwelling Unit

Bedrooms and Bathrooms
Occupancyd
All Days     67     67     67     67     67     67     45     27     0     0     0     0     0     0     0     0     0     0     0     21     21     33     67     67
Lightinge
All Days     0     0     0     0     0     0     66     23     0     0     0     0     0     0     0     0     0     0     0      31     31     47     63     63
Equipmentf
All Days     3     3     3     3     3     3     6     6     3     3     3     3     3     3     3     3     3     3     3     9     9     20     12     12

Other Rooms
Occupancyd
All Days     0     0     0     0     0     0     21     21     21     21     21     21     21     21     21     21     21     67     67     45     45     33     0     0



Lightinge
All Days     0     0     0     0     0     0     29     59     0     0     0     0     0     0     0     0     0     0     0     63     63     47     31     31
Equipmentf
All Days     19     19     19     19     19     19     30     70     34     34     34     61     61     34     34     34     34     84     94     34     34     23     19     19

Notes for Table 13-5:
(a) Reference: Recommendations for Energy Conservation Standards and Guidelines for New Commercial Buildings, Vol. III, App. A. Pacific Northwest Laboratory, PNL-4870-8, 1983.
(b) Table 13-5 contains multipliers for converting the nominal values for building occupancy (Table 13-1), receptacle power density (Table 13-2), service hot water (Table 13-3), and lighting energy (Article 6) into time series data for estimating building loads under the Standard Calculation Procedure. For each standard building profile, there are three series--one each for weekdays, Saturday, and Sunday. There are 24 hours per series. These represent the multiplier that should be used to estimate building loads from 12 a.m. to 1 a.m. (hour No. 1) through 11 p.m. to 12 a.m. (hour No. 24). The estimated load for any hour is simply the multiplier from the appropriate standard profile multiplied by the appropriate value from the tables cited above.
(c) The building HVAC system schedule listed in Table 13-5 lists the hours when the HVAC system shall be considered ON or OFF in accordance with Section 32-13.7(c)(2).
(d) People. Assumes two people per dwelling unit. Maximum heat generation per person = 420 Btu/h (230 Btu/h sensible, 190 Btu/h latent heat).
(e) Lighting. Maximum Installed = 300 Watts.
(f) Equipment. Sensible Heat Gain = [(833 Btu/unit*Number of Living Units) + (0.625 Btu/h-ft2 * Floor Area
of Zone)].
Latent Heat Gain = (0.2 * Sensible Heat Gain).

(Added by Ord. 94-75)

     Article 14. Low-rise Residential Roof Heat Gain Requirements

Sections:
32-14.1    Scope.
32-14.2    Low-rise residential roof heat gain requirements.


Sec. 32-14.1    Scope.
(a)    Notwithstanding Section 32-2.1, the requirements of this article shall apply to low-rise residential buildings and cover new construction and enclosed, habitable additions to existing buildings where the additions are 100 square feet or larger.
(b)    "Roofs" shall mean the same as is defined in Section 32-3.1.
(Added by Ord. 01-46)

Sec. 32-14.2    Low-rise residential roof heat gain requirements.
(a)    The opaque portions of roof assemblies shall include at least one of the following:
    (1)    R-19 insulation between roof or ceiling framing members;
    (2)    Two inches of foam board insulation;
    (3)    A radiant barrier, as provided in subsection (d) and ventilation as provided in subsection (c);
    (4)    A cool roof as provided in subsection (e) and a radiant barrier as provided in subsection (d); or
    (5)    Any construction that meets the opaque roof heat gain requirements of Section 32-8.4(a).
(b)    Plans shall indicate insulation type, thickness, and location; ventilation opening types, sizes and locations; radiant barrier location; and roof surface type as appropriate, depending on the compliance option selected from subsection (a).
(c)    Additional ventilation of the space containing a radiant barrier for compliance with subsection (a)(3) shall be provided by at least one of the following:
    (1)    A baffled ridge vent installed in accordance with the manufacturer's instructions in addition to lower inlet openings to provide a total of no less than one square foot of net free vent area for each 300 square feet of roof area. No less than 30 percent of the total vent area shall be in either the ridge vent or the lower half of the ventilated space.
    (2)    A solar-powered exhaust fan that provides at least one cubic foot per minute of airflow for each square foot of roof area.
    (3)    Upper and lower vents with total net free vent area of at least one square foot for each 150 square feet of roof area. At least 30 percent of the total vent area shall be in the upper half of the ventilated space and at least 30 percent of the total vent area shall be in the lower half of the ventilated space.
(d)    A radiant barrier used for compliance with subsection (a)(3) or (a)(4) shall have an emissivity of no greater than 0.05 as tested per ASTM E-408, Test Method for Total Normal Emittances of Surfaces Using Inspection Meter Techniques (manufacturer's test results are acceptable). The radiant barrier shall be installed with the shiny side facing down and with a minimum air gap thickness of 0.75 inches below. The radiant barrier may be securely attached to the roof framing or may be laminated to the bottom of the roof sheathing.
A radiant barrier is a sheet of material with a low emissivity on at least one side that is used to reduce radiant heat transfer. Radiant barriers typically have a shiny metallic appearance.
(e)    A cool roof for purposes of compliance with subsection (a)(4) shall have a total solar reflectance when tested according to ASTM E-903 of no less than 0.70. The infrared emittance using ASTM E-408 shall be no less than 0.75. The manufacturer's test results shall be acceptable for compliance.
A cool roof has both a light color (high solar reflectance) and a high emittance (can reject heat back to the environment). White painted surfaces and other smooth white coatings typically meet these requirements. Surfaces that do not meet the requirements include unpainted metal and most metalized roof coatings (silver appearance).
(f)    At building sites higher than a 2,400-foot elevation, only subsection (a)(1) or subsection (a)(2) shall be acceptable for compliance.
(g)    For the purpose of this section, "net free vent area" means the total area through which air can pass in a screen, grille face or register.
(h)    For the purpose of this section, "roof area" means attic floor area; or, if there is no attic, "roof area" means the horizontal projection of roof area measured from the outside surface of the exterior walls.
(Added by Ord. 01-46; Am. Ord. 02-34)



Revised Ordinances