Revised Ordinances of Honolulu(Link to original Word Processing Version)
Articles:
(1) Amending Section 101.1. Section 101.1 is amended to read as follows:
101.1 Title . This code shall be known as the Building Energy Conservation Code
of the City and County of Honolulu, and shall be cited as such.
It is referred to herein as "this code."
(2) Amending Section 101.5.2. Section 101.5.2 is amended to read as follows:
101.5.2 Low Energy Buildings . The following buildings, or portions thereof, separated from the
remainder of the building by building thermal envelope assemblies complying with this code
shall be exempt from the building thermal envelope provisions of this code:
1. Conditioned spaces with a peak design rate of energy usage less than 3.4
Btu/h·ft2 (10.7 W/m2) or 1.0 watt/ft2 (10.7 W/m2) of floor area for space
conditioning purposes.
2. Unconditioned spaces that are non-habitable spaces.
(3) Amending Section 104.1. Section 104.1 is amended to read as follows:
104.1 General . When the requirements in this code apply to a building as
specified in Section 101.4, plans, specifications or other construction documents submitted for a
building, electrical, or plumbing permit required by this jurisdiction shall comply with this
code and shall be prepared, designed, approved, and observed by a design professional.
The responsible design professional shall provide on the plans a signed statement certifying
that the project is in compliance with this code.
Exception : Any building, electrical, or plumbing work that is not required to be
prepared, designed, approved, or observed by a licensed professional architect or engineer pursuant
to Chapter 464 of the Hawaii Revised Statutes.
104.3 Conformance Statement . The plan shall include the following conformance statement by the
responsible engineer or architect that the design conforms to this code.
________ Building Component Systems
Signature:_____________________________ Date:____________________
(5) Deleting Section 105. Section 105 is deleted.
(6) Amending Table 402.1.1. Table 402.1.1 is amended to read as follows:
a. R-values are minimums. U-factors and SHGC are maximums. R-19 shall be permitted
to be compressed into a 2 × 6 cavity.
b. The fenestration U-factor column excludes skylights. The SHGC column applies to all
glazed fenestration.
c. The first R-value applies to continuous insulation, the second to framing cavity
insulation; either insulation meets the requirement.
d. R-5 shall be added to the required slab edge R-values for heated
slabs.
e. There are no SHGC requirements in the Marine zone.
f. Or insulation sufficient to fill the framing cavity, R-19 minimum.
g. "13+5" means R-13 cavity insulation plus R-5 insulated sheathing. If structural sheathing
covers 25 percent or less of the exterior, insulating sheathing is not required
where structural sheathing is used. If structural sheathing covers more than 25 percent
of exterior, structural sheathing shall be supplemented with insulated sheathing of at least
R-2.
402.1.1.1 Ceiling Insulation Alternative . Insulation requirements for ceilings in buildings constructed in climate
zone 1 shall meet one of the design options in Table 402.1.1.1.
Gross Area of Opaque Roof Surfaces. Gross area of opaque roof surfaces means
the total surface of the roof assembly exposed to outside air or unconditioned
spaces. The opaque roof assembly shall exclude skylight surfaces, service openings, and overhangs.
Net Free Vent Area. Net free vent area means the total area through
which air can pass in a screen, grille face or register.
Roof Area. Roof area means attic floor area; or, if there is no
attic, "roof area" means the horizontal projection of roof area measured from the
outside surface of the exterior walls.
402.1.1.3 Construction Documents . Plans shall be submitted which indicate insulation type, thickness, and
location; ventilation opening types, sizes and locations; radiant barrier location; and, roof surface
type as appropriate, depending on the option selected from Table 402.1.1.1.
402.1.1.4 Roof Insulation . Roof insulation shall be provided as follows:
1. In buildings with an attic space provide either:
1.1. R-30 insulation installed above the ceiling level, or
1.2. R-19 insulation installed at the roof level between the roof framing members.
2. In buildings without an attic space provide either:
402.1.1.6 Radiant Barrier . A radiant barrier shall have an emissivity of no greater
than 0.05 as tested in accordance with ASTM E-408. The radiant barrier shall
be installed with the shiny side facing down and with a minimum air
gap thickness of three-fourths (¾ ) inch. The radiant barrier may be securely
attached to the roof framing or may be laminated to the bottom of
the roof sheathing.
402.1.1.7 Cool Roof . A cool roof shall have an infrared emittance of no
more than 0.75 when tested in accordance with ASTM E-408 and a high
solar reflectance. The manufacturer's test results shall be acceptable for compliance.
402.1.1.8 Roof Heat Gain Factor . The Roof Heat Gain Factor (RHGF) shall not
exceed 0.05 when calculated as described in Equation 402.1.1-1.
Equation 402.1.1-1
Where:
RHGF = Roof Heat Gain Factor (Btu/ft2-h-°F)
Ur = Overall thermal transmittance value for the gross area of opaque roof
surfaces (Btu/ft2-h-°F)
α = Roof surface absorptivity. Between 0.3 and 1.0 (unitless)
RB = Radiant Barrier credit. Equals 0.33 if a radiant barrier is installed
and 1.00 otherwise (unitless). Radiant barrier installation shall comply with Section 402.1.1.7.1 to
qualify for Radiant Barrier credit.
402.1.1.8.1 Radiant Barrier Credit . To qualify for the Radiant Barrier credit (RB) described
in Section 402.1.1.8, the installation of the radiant barrier shall meet the following
criteria:
1. The emissivity of the radiant barrier shall be 0.10 or less. The manufacturer
shall provide test data or documentation of the emissivity as tested in accordance
with ASTM E-408.
2. The radiant barrier shall be securely installed in a permanent manner using one
of the following installation methods:
2.1. The radiant barrier shall be draped with the reflective surface facing down over
the top cord of the truss before the roof deck is installed. A
minimum air gap of three-fourths (¾) inch shall be provided between the radiant
barrier and the roof deck above at the center of the span. A
minimum three-fourths (¾) inch air gap shall also be provided between the radiant
barrier and the ceiling or insulation below.
2.2. The radiant barrier shall be stretched with the shiny side facing down between
the top cords of the truss and stapled or otherwise secured at each
side. A minimum air space of three-fourths (¾) inch above and below is
required.
2.3. For attic installations only, the radiant barrier shall be stapled or otherwise secured
to the bottom surface of the top cord of the truss and draped
below with the shiny side facing down. A minimum air space of three-fourths
(¾) inch above and below is required.
2.4. For open beam ceiling construction only, the radiant barrier shall be laid on
top of the roof deck with the shiny side facing up and a
minimum three-fourths (¾) inch air gap between the radiant barrier and the roofing
material above. The roof slope shall be greater than or equal to 14°
from horizontal.
3. At least one square foot of free area for ventilation shall be provided
per 150 square feet of attic floor area, or in the case of
vaulted or open-beam ceilings, per 150 square feet of ceiling area. In vaulted
or open beam ceilings, the air space shall have an evenly-distributed vent area.
In vaulted ceilings, vents shall be provided for each air space between rafters.
(8) Amending Table 402.1.3. Table 402.1.3 is amended to read as follows:
a. Nonfenestration U-Factors shall be obtained from measurement, calculation or an approved source.
402.3.3 Glazed Fenestration Exemption . Up to 15 square feet (1.4 m2) of glazed
fenestration per dwelling unit shall be permitted to be exempt from U-factor and
SHGC requirements in Section 402.1.1. North-facing windows and windows with a projection factor
of 1.0 or more shall be permitted to be exempt from SHGC requirements
in Section 402.1.1.
(10) Amending Section 402.4.1. Section 402.4.1 is amended by adding Section 402.4.1.1 to read
as follows:
402.4.1.1 Unconditioned building exemption. Unconditioned residential buildings are exempt from compliance with Section
402.4. The free-vent fenestration area of unconditioned buildings shall be no less than
14 percent of the floor area. All interior doors shall be capable of
being secured in the open position and ceiling fan stub-ins shall be provided
to living areas and bedrooms.
(11) Amending Section 402.4.2. Section 402.4.2 is amended to read as follows:
402.4.2 Fenestration Air Leakage . Windows, skylights and sliding glass doors shall have an
air infiltration rate of no more than 0.3 cfm per square foot (1.5
L/s/m2), and swinging doors no more than 0.5 cfm per square foot (2.6
L/s/m2), when tested according to NFRC 400 or AAMA/WDMA/CSA 101/I.S.2/A440 by an accredited,
independent laboratory and listed and labeled by the manufacturer.
Exceptions:
2. Jalousie windows shall not exceed 1.2 cfm per square foot (6.1 L/s/m2).
403.7.1 Pool Heaters. All pool heaters shall be equipped with a readily accessible
on-off switch to allow shutting off the heater without adjusting the thermostat setting.
Pool heaters fired by natural gas shall not have continuously burning pilot lights.
403.7.2 Time Switches . Time switches that can automatically turn off and on heaters
and pumps according to a preset schedule shall be installed on swimming pool
heaters and pumps.
Exceptions:
2. Where pumps are required to operate solar- and waste-heat-recovery pool heating systems.
403.7.3 Pool Covers. Heated pools shall be equipped with a vapor retardant pool
cover on or at the water surface. Pools heated to more than 90oF
(32oC) shall have a pool cover with a minimum insulation value of R-12.
Exception: Pools deriving over 60 percent of the energy for heating from site-recovered energy
or solar energy source.
(14) Adding a new Section 503.2.9. A new Section 503.2.9 is added to read
as follows:
503.2.9 Mechanical Systems Commissioning and Completion Requirements . Prior to the issuance of a
certificate of occupancy, the design professional shall provide a written statement of system
completion in accordance with Sections 503.2.9.1 through 503.2.9.2.
503.2.9.1 System Commissioning. Commissioning is a process that verifies and documents that the
selected building systems have been designed, installed, and function according to the owner's
project requirements and construction documents. Drawing notes shall require commissioning and completion requirements
in accordance with this section. Drawing notes may refer to specifications for further
requirements. Copies of all documentation shall be given to the owner.
503.2.9.1.1 Commissioning Plan . A commissioning plan shall include, as a minimum, the following
items:
1. A detailed explanation of the original owner's project requirements;
2. A narrative describing the activities that will be accomplished during each phase of
commissioning, including guidance on who accomplishes the activities and how they are completed;
3. Equipment and systems to be tested, including the extent of tests;
4. Functions to be tested (for example, calibration, economizer control, etc.);
5. Conditions under which the test shall be performed (for example, winter and summer
design conditions, full outside air, etc.); and
6. Measurable criteria for acceptable performance.
503.2.9.2 Systems Adjusting and Balancing . All HVAC systems shall be balanced in accordance
with generally accepted engineering standards. Air and water flow rates shall be measured
and adjusted to deliver final flow rates within 10 percent of design rates.
Test and balance activities shall include, as a minimum, the following items:
1. Air systems balancing: Each supply air outlet and zone terminal device shall be
equipped with means for air balancing in accordance with the requirements of Chapter
6 of the International Mechanical Code. Discharge dampers are prohibited on constant volume
fans and variable volume fans with motors 10 hp (18.6 kW) and larger.
Air systems shall be balanced in a manner to first minimize throttling losses;
then, for fans with a system power greater than 1 hp, fan speed
shall be adjusted to meet design flow conditions.
Exception : Fan with fan motors of 1 hp or less.
2. When throttling results are no greater than 5 percent of the nameplate horsepower
draw above that required if the impeller were trimmed.
ASTM E 408-2008, Standard Test Methods for Total Normal Emittance of Surfaces Using
Inspection Meter Techniques
.402.1.1.6, 402.1.1.7, 402.1.1.8.1.
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||