Revised Ordinances of Honolulu

(Link to original Word Processing Version)


    Article 5. Energy Conservation

Sections:
    16-5.1     Scope--Applicability--Information for plans and specifications-- Alternative systems.
    16-5.2     Definitions.
    16-5.3     Exterior envelope requirements.
    16-5.4     Warm air heating, ventilating and air-conditioning systems--All occupancies except Group R, Division 3 occupancies.
    16-5.5     Warm air heating, ventilating and air-conditioning systems in one- and two-family dwellings--Group R, Division 3 occupancies.
    16-5.6     Systems controls in all occupancies.
    16-5.7     Piping for steam and hot water heating systems.
    16-5.8     Conservation of hot water.
    16-5.9     Controls.
    16-5.10    Lighting power limit for buildings.
    16-5.11    Energy conservation in electrical distribution systems.
    16-5.12    Violation--Penalty.

Sec. 16-5.1    Scope--Applicability--Information for plans and specifications-- Alternative systems.
(a)    Scope. This article shall apply only to low-rise residential buildings that are exempted from the provisions of Chapter 32. The provisions of this article regulate the design and construction of the exterior envelopes of, and selection of heating, ventilating and air conditioning, service water heating, electrical distribution and illuminating systems and equipment required for the purpose of effective conservation of energy within, a building or structure governed by this code. Compliance with applicable provisions of ASHRAE Standard No. 90A-80 shall be deemed to meet the requirements of this article.
(b)    Applicability.
    (1)    The energy efficiency building standards shall be enforced at the time of construction of a new building and shall also be applied, in part, to that portion of a major addition, alteration or repair of an existing building when the proposed major addition, alteration or repair must comply with the standards applicable to new buildings under the building code.
    (2)    Exceptions.
        (A)    Buildings and structures, or portions thereof, which are not heated or cooled shall be exempt from the provisions of Sections 16-5.3 through 16-5.6 regulating exterior envelope and heating, ventilating and air-conditioning system.
        (B)    Buildings and structures whose peak design rate of energy usage is less than one watt per square foot or 3.4 Btu/h per square foot of floor area for all purposes shall be exempt from all provisions of this article.
        (C)    Structures which are not heated or cooled, or where cooled with air conditioning systems totaling less than 12,000 Btu/h capacity, shall be exempt from all provisions of this article except Sections 16-5.8 and 16-5.9 pertaining to the conservation of hot water.
        (D)    For special applications such as hospitals, laboratories, thermally sensitive equipment, computer rooms, and manufacturing and industrial processes, the design concepts and parameters shall conform to the requirements of the application at minimum energy levels.
(c)    Plans and Specifications. Plans, specifications and necessary computations shall be submitted to indicate conformance with this article. Plans and specifications for work to comply with the provisions of this article shall be prepared, designed or approved by a duly registered professional engineer or architect as required by HRS Chapter 464.
(d)    Information on Plans and Specifications. The plans and specifications shall show in sufficient detail all pertinent data and features of the building and the equipment and systems as herein governed including but not limited to: exterior envelope component materials, U values of the respective elements including insulation, R values of insulating materials, size and type of apparatus and equipment, equipment and system controls, and other pertinent data to indicate conformance with the requirements of this article.
(e)    Alternative Systems.
    (1)    Alternative building systems and equipment design shall be approved by the building official when it can be demonstrated that the proposed energy consumption will not exceed that of a similar building with similar forms of energy requirements designed in accordance with the provisions of this article.
    (2)    When such alternative systems utilize solar, geothermal, wind or other nondepletable energy sources or utilize waste heat for all or part of its energy sources, such nondepletable energy or recovered waste heat supplied to the buildings may be excluded from the total energy chargeable to the proposed alternative design.
    (3)    Proposed alternative designs submitted as requests for exception to the standard design criteria must be accompanied by an energy analysis prepared in accordance with established principles of environmental technologies (such as ASHRAE Standard 90).
(Sec. 16-7.1, R.O. 1978 (1987 Supp. to 1983 Ed.); Am. Ord. 90-57, 94-75, 97-16)

Sec. 16-5.2    Definitions.
    The following terms are defined for specialized use within this article.
    "ASHRAE" means American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
    "Coefficient of performance (COP)--Cooling" means:
    (1)    Electrically Operated HVAC Equipment. The ratio of the rate of net heat removal to the rate of total energy input expressed in consistent units and under designated rating conditions. The rate of net heat removal as used within this definition shall be the change in the enthalpies of the air entering and leaving the equipment (without reheat). The total energy inputs as used within this definition shall be determined by combining the energy inputs to all elements of the equipment, including, but not limited to, compressors, pumps, supply-air fans, return-air fans, condenser-air fans, cooling tower fans and pumps, and the heating, ventilating and air-conditioning system equipment control circuit.
    (2)    Applied HVAC System Components. The ratio of the rate of net heat removal to the rate of total energy input expressed in consistent units and under designated rating conditions. The rate of net heat removal as used within this definition shall be the difference in enthalpies of the water or refrigerant entering and leaving the component. The total energy input as used within this system shall be determined by combining the energy inputs to all elements and accessories of the component, including, but not limited to, compressors, internal circulating pumps, condenser-air fans, evaporative-condenser cooling water pumps, purge, and the heating, ventilating and air-conditioning system components control circuit.
    (3)    Heat-operated HVAC System Equipment. The ratio of the net cooling output to the total heat input. The rate of net heat removal as used within this definition shall be the difference in enthalpies of the water or refrigerant entering and leaving the component. The total energy input as used within this system shall be determined by combining the energy inputs to all elements and accessories of the component, including, but not limited to, compressors, internal circulating pumps, condenser-air fans, evaporative-condenser cooling water pumps, purge and the heating, ventilating and air-conditioning system components control circuit.
    "Coefficient of performance (COP)--heat pump, heating" means the ratio of the rate of net heat output to the rate of total energy input expressed in consistent units and under designated rating conditions. The rate of net heat output as used within this definition shall be the change in the total heat contents of the air entering and leaving the equipment, excluding supplementary heat. The total energy input as used within this definition shall be the combined energy inputs to all elements except supplementary heaters of the heat pump, including, but not limited to, compressors, pumps, supply-air fans, return-air fans, outdoor-air fans, cooling-tower fans and the HVAC system equipment control circuit.
    "Energy efficiency ratio (EER)" means the ratio of net cooling capacity in Btuh to total rate of electric input in watts under designated operating conditions.
    "Exterior envelope" means the elements of a building which enclose conditioned spaces through which thermal energy may be transferred to or from the exterior, or from unconditioned spaces.
    "Exterior walls" means, for the purpose of this article, the gross area of exterior walls consisting of all opaque wall areas and partition areas, including foundation walls above grade, peripheral edges of floors, window areas including sash, and door areas, where such surfaces are exposed to outdoor air or unconditioned interior space and enclose a heated or mechanically cooled space.
    "Fenestration" means any light-transmitting opening in a building wall or roof. Included are (1) the glazing material which may be glass or plastic, (2) the framing, mullions, muntins and dividers, (3) external shading devices, (4) internal shading devices, and (5) integral (between-glass) shading systems.
    "Floor area, gross" means the floor area within the perimeter of the outside walls of the building under consideration, without deduction for hallways, stairs, closets, thickness of walls, columns or other features.
    "Heated space" means a space within a building which is provided with a positive heat supply to maintain air temperature of 50 degrees Fahrenheit or higher.
    "HVAC" means heating, ventilation and air-conditioning.
    "Opaque areas" means all exposed areas of a building envelope which enclose conditioned space, except openings for windows, skylights, doors and building service systems.
    "Packaged terminal air conditioner" means a factory-selected combination of heating and cooling components, assemblies or sections, intended to serve a room or zone.
    "Power factor" means the ratio of the true power (watts) to the apparent power (volts x amperes); the cosine of the angle of lag between the alternating current and the voltage waves.
    "Rate of net heat output" means the change in the total heat contents of the air entering and leaving the equipment, not including supplementary heat.
    "Readily accessible" means capable of being reached safely and quickly for operation, repair or inspection without requiring those of whom ready access is requisite to climb over or remove obstacles or to resort to the use of portable access equipment.
    "Reheat" means the application of sensible heat to supply air that has been previously cooled below the temperature of the conditioned space by either mechanical refrigeration or the introduction of outdoor air to provide cooling.
    "Roof assembly" means:
    (1)    For the purpose of this article, a roof assembly shall be considered as all components of the roof/ceiling envelope through which heat flows, thereby creating a building transmission heat loss or gain, where such assembly is exposed to outdoor air and encloses a heated or mechanically cooled space.
    (2)    The gross area of a roof assembly consists of the total interior surface of such assembly, including skylights, exposed to the heated and/or mechanically cooled space.
    (3)    Where ceiling air plenums are employed, the roof/ceiling assembly shall:
        (A)    For thermal transmittance purposes, not include the ceiling proper nor the plenum space as part of the assembly.
        (B)    For gross area purposes, be based upon the interior face of the upper plenum surface.

    Shading Coefficient (SC).

SC =
OLE Object Here


Where:    DS means double strength
    B means grade class

    "Supplementary heat" means heat generated in a heat pump, electrical resistance heat or other heat input not provided through the heat pump cycle.
    "Terminal element" is the means by which the transformed energy from a system is finally delivered; i.e., registers, diffusers, lighting fixtures, faucets, etc.
    "Thermostat" means an instrument which measures changes in temperature and controls device(s) for maintaining a desired temperature.
    "Unconditioned" means not heated or cooled.
    "Zone" means a space or group of spaces within a building with heating or cooling requirements sufficiently similar so that comfort conditions can be maintained throughout by a single controlling device. (Sec. 16-7.2, R.O. 1978 (1987 Supp. to 1983 Ed.); Am. Ord. 90-57)

Sec. 16-5.3    Exterior envelope requirements.
(a)    General.
    (1)    The intent of this section is to provide minimum requirements for exterior envelope construction.
    (2)    In addition to the criteria set forth in this article, the proposed design may take into consideration the thermal mass of the building in considering energy conservation in accordance with engineering design standards such as those of ASHRAE.
    (3)    A building that is designed to be both heated and cooled shall meet the more stringent of the heating and cooling requirements of the exterior envelope as provided in this section when the requirements differ.
(b)    Thermal Performance.
    (1)    All buildings and structures, or portions thereof, that are heated or mechanically cooled shall be constructed so as to provide the required thermal performance of the various components.
    (2)    The required thermal transmittance value (Uo) of any one component such as roof/ceiling, wall or floor may be increased and the Uo value for any other components decreased provided that the overall heat gain or loss for the entire building envelope does not exceed the total resulting from conformance to the required Uo values.
(c)    Residential Buildings Not More Than Three Stories in Height. The following provisions shall apply to all buildings and structures, or portions thereof, not more than three stories in height and housing Group R occupancies.
    (1)    Walls. The gross area of exterior walls above grade, including foundation walls, shall have a combined thermal transmittance value (Uo) not exceeding those specified in Table No. 16-5A. The combined thermal transmittance value (Uo) is to be computed using Equation 16-5.1.
        EXCEPTIONS. In locations with less than 500 Fahrenheit heating degree days, there shall not be a maximum Uo requirement if only heating is provided, and the Uo shall not exceed those specified in Table No. 16-5A if the building is mechanically cooled.


Uo =
OLE Object Here
………………(16-5.1)


        Note. Where more than one type of wall, window and/or door is used, the U x A term for that exposure shall be expanded into its subelements, as:

            Uwall1 Awall1 + Uwall2, etc.

    Where Uo    =    the average thermal transmittance of the gross wall area, Btu/hft2F.
        Ao    =    the gross area of exterior walls, ft2.
        Uwall    =    the thermal transmittance of all elements of the opaque wall area, Btu/hft2F.
        Awall    =    opaque wall area, ft2.
        Uwindow =    the thermal transmittance of the window area, Btu/hft2F.
        Awindow =    window area (including sash), ft2.
        Udoor    =    the thermal transmittance of the door area, Btu/hft2F.
        Adoor    =    door area, ft2.
    (2)    Roof/Ceiling. Any building that is heated or mechanically cooled shall have a combined thermal transmittance value (Uo) for roof/ceiling not exceeding those specified in Table No. 16-5A. The combined thermal transmittance value (Uo) is to be computed using Equation 16-5.2.

        Uo=


OLE Object Here
……………………………..(16-5.2)

Note. Where more than one type of roof/ceiling and/or skylight is used, the U x A term for that exposure shall be expanded into its subelements, as:

            Uroof1 Aroof1 + Uroof2 Aroof2, etc.

            Where Uo = the average thermal transmittance of the gross roof/ceiling area, Btu/hft2F.
            Ao = the gross area of a roof/ceiling assembly, ft2.
            Uroof = the thermal transmittance of all elements of the opaque roof/ceiling area, Btu/hft2F.
            Aroof = opaque roof/ceiling area, ft2.
            Uskylight = the thermal transmittance of all skylight elements in the roof/ceiling assembly, Btu/hft2F.
            Askylight = skylight area (including frame), ft2.
    (3)    Floors Over Unheated Spaces. The floor of a heated or mechanically cooled space located over an unheated space shall have a combined thermal transmittance value (Uo) as specified in Table No. 16-5A.
(d)    Other Buildings. The following provisions shall apply to all buildings and structures, or portions thereof, except those covered within subsection (c) of this section.
    (1)    Heating Criteria for Walls. All buildings and structures, or portions thereof, that are heated shall have a combined thermal transmittance value (Uo) for the gross area of exterior walls not exceeding those specified in Table No. 16-5B. The combined thermal transmittance value (Uo) is to be computed using Equation 16-5.1.
    (2)    Heating Criteria for Roof/Ceiling. All buildings and structures, or portions thereof, that are heated shall have a combined thermal transmittance value (Uo) for roof/ceiling assemblies not exceeding those specified in Table No. 16-5B. The combined thermal transmittance value (Uo) is to be computed using Equation 16-5.2.
    (3)    Heating Criteria for Floors Over Unheated Spaces. The floor of a heated space located over an unheated space shall have a thermal transmittance value (Uo) not exceeding those specified in Table No. 16-5B.
    (4)    Cooling Criteria for Walls. All buildings and structures, or portions thereof, that are mechanically cooled shall have an overall thermal transfer value for the gross area of exterior walls not exceeding those specified in Table No. 16-5B. The overall thermal transfer value, OTTV, for the gross area of exterior walls is to be computed using Equation 16-5.3.

        OTTV =


OLE Object Here
………………………(16-5.3)

        Note. Where more than one type of wall and/or fenestration is used, the terms shall be expanded into subelements, as:

        (U(wall x Awall x TDEQ) + (Uwall2 x Awall2 x TDEQ2) etc.

        Where OTTV = overall thermal transfer value.
        Uwall = the thermal transmittance of all elements of the opaque wall area, Btu/hft2F.
        Awall = opaque wall area, ft2.
        Uf     = the thermal transmittance of the fenestration area, Btu/hft2F.
        Af    = entire exterior wall fenestration area, ft2.
        TDEQ    = value given in Table No. 16-5H.
        SC    = shading coefficient of the fenestration (see Section 16-5.2).
        Ao    = gross area of exterior walls, ft2.
        ΔT    = temperature difference between exterior and interior design conditions, F.
        SF    = solar factor value given in Btu/h-ft2, using value from the following table for the peak load time of the cooling system:


SF (Interpolate for Other Directions and Times)1
 
Time  
N   NE   E   SE   S   SW   W   NW   Horiz.  
8 a.m.  
21  
134   227   186   36   20   20   20   116  
10 a.m.  
32  
61   161   168   76   33   32   32   238  
12 noon  
36  
37   39   69   93   69   39   37   282  
2 p.m.  
32  
32   32   33   76   168   161   61   238  
4 p.m.  
21  
20   20   20   36   186   227   134   116  
1 Where construction has exterior shading such that no sun heat can reach the glass at all hours, its solar factor shall be taken as 21.  
    (5)    Cooling Criteria for Roof/Ceilings. All buildings and structures, or portions thereof, that are mechanically cooled shall have a combined thermal transmittance value (Uo) for roof/ceiling assemblies not exceeding those specified in Table No. 16-5B. The combined thermal transmittance value (Uo) is to be computed using Equation 16-5.2.
(Sec. 16-7.3, R.O. 1978 (1987 Supp. to 1983 Ed.); Am. Ord. 90-57)

Sec. 16-5.4    Warm air heating, ventilating and air-conditioning systems--All occupancies except Group R, Division 3 occupancies.
(a)    Scope. This section applies to air duct systems employing mechanical means for the movement of air used for warm air heating, cooling, ventilation, air-conditioning systems, exhaust systems, and combination heating and air-conditioning systems, except that this section shall not apply to systems for the removal of flammable vapors or residues or to systems for conveying dust, stock or refuse by means of air currents.
    (1)    Design Parameters. For calculations under this section, the following design parameters shall apply:
        (A)    Outdoor design conditions shall be based on requirements in Chapter 39 -- Air Conditioning and Ventilating of the Administrative Rules of the Department of Health, State of Hawaii.
        (B)    Indoor design temperature shall be 70 degrees Fahrenheit for heating and 77 degrees Fahrenheit for cooling.
        (C)    Indoor design relative humidity for heating shall not exceed 30 percent. For cooling, the design relative humidity shall be 50 percent.
    (2)    Mechanical Ventilation. Each mechanical ventilation system shall be equipped with an accessible means for either shutoff or volume reduction and shutoff when ventilation is not required.
    (3)    Simultaneous Heating and Cooling. Systems that employ both heating and cooling simultaneously in order to achieve comfort conditions within a space shall be limited to those situations where more efficient methods of heating and air conditioning cannot be effectively utilized to meet system objectives. Simultaneous heating and cooling by reheating or recooling supply air or by concurrent operation of independent heating and cooling systems serving a common zone shall be restricted as specified herein.
        (A)    New energy may be used for control of temperature if minimized as specified in subparagraphs (C) through (H) of this paragraph. New energy is defined as energy, other than recovered, utilized for the purpose of heating or cooling.
        (B)    Recovered energy, provided the new energy expended in the recovery process is less than the amount recovered, may be used for control of temperature and humidity.
        (C)    New energy may be used, when necessary, to prevent relative humidity from rising above 80 percent for comfort control or to prevent condensation on terminal units or outlets.
        (D)    Systems employing reheat and serving multiple zones, other than those employing variable air volume for temperature control, shall be provided with control that will automatically reset the system cold air supply to the highest temperature level that will satisfy the zone requiring the coolest air. Single zone reheat systems shall be controlled to sequence cooling reheating.
        (E)    Dual duct and multi-zone systems shall be provided with control that will automatically reset the cold air supply to the highest temperature that will satisfy the zone requiring the coolest air and the hot air supply to the lowest temperature that will satisfy the zone requiring the warmest air.
        (F)    Systems in which heated air is recooled, directly or indirectly, to maintain space temperature, shall be provided with control that will automatically reset the temperature to which the supply air is heated to the lowest level that will satisfy the zone requiring the warmest air.
        (G)    For systems with multiple zones, one or more zones may be chosen to represent a number of zones with similar heating/cooling characteristics. A multiple zone heating, ventilating and air-conditioning system that employs reheating or recooling for control of not more than 5,000 cfm or 20 percent of the total supply air of the system, whichever is less, shall be exempt from the supply air temperature reset requirements of subparagraphs (D) and (F) of this paragraph.
        (H)    Concurrent operation of independent heating and cooling systems serving common spaces and requiring the use of new energy for heating or cooling shall be minimized by one or both of the following:
            (i)    By providing sequential temperature control of both heating and cooling capacity in each zone.
            (ii)    By limiting the heating energy input, through automatic reset control of the heating medium temperature or energy input rate, to only that necessary to offset heat loss due to transmission and infiltration and, where applicable, to heat the ventilation air supply to the space.
(b)    Equipment Performance Requirements. The requirements of this section apply to equipment and component performance for heating, ventilating and air-conditioning systems. Where equipment efficiency levels are specified, data furnished by the equipment supplier or certified under a nationally recognized certification program or rating procedure shall be used to satisfy these requirements.
    (1)    System Equipment.
        (A)    Heating, ventilating and air-conditioning system equipment whose energy input in the cooling mode is entirely electric shall show a coefficient of performance (COP) and energy efficiency ratio (EER) not less than the values specified in Table No. 16-5C. These requirements apply to, but are not limited to, unitary cooling equipment (air and water source), packaged air conditioners and room air conditioners. This paragraph does not apply to equipment used in areas having open refrigerated food display cases.
        (B)    Heat-operated cooling equipment shall show a coefficient of performance (COP) in the cooling mode not less than the values specified in Table No. 16-5D. These requirements apply to, but are not limited to, absorption, engine-driven and turbine-driven equipment. The coefficient of performance (COP) is determined excluding the electrical auxiliary inputs.
    (2)    System Components. Heating, ventilating and air-conditioning system components whose energy input in the cooling mode is entirely electric shall show a coefficient of performance (COP) and energy efficiency ratio (EER) not less than the values specified in Table No. 16-5E.
    (3)    Heat Pumps. Heat Pumps whose energy input is entirely electric shall show a coefficient of performance (COP), heating, not less than the values specified in Table No. 16-5F.
    (4)    Supplementary Heater.
        (A)    The heat pump shall be installed with a control to prevent supplementary heater operation when the heating load can be met by the heat pump alone.
        (B)    Supplementary heater operation is permitted during transient periods, such as start-ups, following room thermostat set-point advance and during defrost.
        (C)    A two-stage room thermostat which controls the supplementary heat in its second stage shall be accepted as meeting this requirement. The cut-on temperature for the compression heating shall be higher than the cut-on temperature for the supplementary heat, and the cut-off temperature for the compression heating shall be higher than the cut-off temperature for the supplementary heat. Supplementary heat may be derived from any source of electric resistance heating or combustion heating.
    (5)    Combustion Heating Equipment. All gas and oil-fired comfort heating equipment shall show a minimum combustion efficiency of 75 percent at maximum rated output. Combustion efficiency shall be determined in accordance with acceptable engineering principles.
(c)    Insulation of Ducts. All duct systems, or portions thereof, exposed to nonconditioned spaces shall be insulated in accordance with UBC Section 707.4.
(Sec. 16-7.4, R.O. 1978 (1987 Supp. to 1983 Ed.); Am. Ord. 90-57, 97-16)

Sec. 16-5.5    Warm air heating, ventilating and air-conditioning systems in one- and two-family dwellings-- Group R, Division 3 occupancies.
    All duct systems, or portions thereof, exposed to nonconditioned spaces shall be insulated in accordance with UBC Section 707.4. (Sec. 16-7.5, R.O. 1978 (1987 Supp. to 1983 Ed.); Am. Ord. 90-57, 97-16)

Sec. 16-5.6    Systems controls in all occupancies.
    All heating, ventilating and air-conditioning systems shall be provided controls for all occupancies as specified herein.
(a)    Temperature. Each heating, ventilating and air-conditioning system shall be provided with at least one thermostat for the regulation of temperature. Each thermostat shall be capable of being set from 55 degrees Fahrenheit to 75 degrees Fahrenheit, where used to control cooling only. Where used to control both heating and cooling, it shall be capable of being set from 55 degrees Fahrenheit to 85 degrees Fahrenheit, and shall be capable of operating the system heating and cooling in sequence. It shall be adjustable to provide a temperature range of up to 10 degrees Fahrenheit between full heating and full cooling, except as allowed, in Section 16-5.4 (a)(3)(H).
(b)    Humidity. If a heating, ventilating, and air-conditioning system is equipped with a means for adding moisture to maintain specific selected relative humidities in spaces or zones, a humidistat shall be provided. This device shall be capable of being set to prevent new energy from being used to produce space relative humidity above 30 percent relative humidity. Where a humidistat is used in a heating, ventilating and air-conditioning system for controlling moisture removal to maintain specific selected relative humidities in spaces or zones, it shall be capable of being set to prevent new energy from being used to produce a space relative humidity below 60 percent.
(c)    Temperature Zoning.
    (1)    In all Group R, Division 3 occupancies, at least one thermostat for regulation of space temperature shall be provided for each separate heating, ventilating and air-conditioning system. In addition, a readily accessible manual or automatic means shall be provided to partially restrict or shut off the heating or cooling input to each zone or floor, excluding unheated or uncooled basements and garages.
    (2)    In all Group R, Division 1 occupancies, each individual dwelling unit shall be considered separately and shall meet the above requirements for Group R, Division 3 occupancies.
    (3)    In all buildings and structures, or portions thereof, other than Group R, Division 3 occupancies, and in spaces other than dwelling units in Group R, Division 1 occupancies, at least one thermostat for regulation of space temperature shall be provided for each separate heating, ventilating and air-conditioning system and for each floor of the building.
(d)    Setback and Shut Off.
    (1)    In all Group R, Division 3 occupancies, the thermostat or an alternate means such as a switch or a clock shall provide a readily accessible manual or automatic means for reducing the energy required for heating and cooling during periods of nonuse or reduced need.
    (2)    In all other buildings and structures, or portions thereof, each heating, ventilating and air-conditioning system shall be equipped with a readily accessible means of reducing the energy used for heating, ventilating and air-conditioning during periods of nonuse or alternate uses of the building spaces or zones served by the system, such as with manually adjustable automatic timing devices, manual devices for use by operating personnel or automatic control systems.
    (3)    Lowering thermostat set points to reduce energy consumption of heating systems shall not cause energy to be expended to reach the reduced setting.
(Sec. 16-7.6, R.O. 1978 (1987 Supp. to 1983 Ed.); Am. Ord. 90-57)

Sec. 16-5.7    Piping for steam and hot water heating systems.
(a)    All piping serving as part of a heating or cooling system installed to serve buildings and within buildings shall be thermally insulated as shown in Table No. 16-5G.
(b)    Insulation thicknesses are based on insulation having thermal resistance in the range of 4.0 to 4.6 per inch of thickness on a flat surface at a mean temperature of 75 degrees Fahrenheit. Minimum insulation thickness shall be increased for materials having R values less than 4.0 or may be reduced for materials having R values greater than 4.6 per inch of thickness as follows:
    (1)    For materials with thermal resistance greater than R = 4.6, the minimum insulation thickness may be determined as follows:


OLE Object Here
= New Minimum Thickness


    (2)    For materials with thermal resistance less than R = 4.0, the minimum insulation thickness shall be determined as follows:


OLE Object Here
= New Minimum Thickness



        EXCEPTIONS. Piping insulation, except when needed to prevent condensation, is not required in any of the following cases:
        (A)    Piping installed within heating, ventilating and air-conditioning equipment.
        (B)    Piping operating at internal temperatures between 55 degrees Fahrenheit and 120 degrees Fahrenheit.
        (C)    When the heat loss or heat gain of the piping, without insulation, does not increase the energy requirements of the building.
        (D)    Piping installed in basements, cellars or unventilated crawl space with insulated walls in Group R, Division 3 occupancies.
    Where required to prevent condensation, insulation with vapor barriers shall be installed in addition to insulation required above.
(Sec. 16-7.7, R.O. 1978 (1987 Supp. to 1983 Ed.); Am. Ord. 90-57)

Sec. 16-5.8    Conservation of hot water.
(a)    Showers. Showers used for other than safety reasons shall be equipped with flow control devices to limit total flow to a maximum of three gpm per shower- head.
(b)    Lavatories. Lavatories with hot water supplies in rest rooms of other than dwelling units in Group R occupancies shall:
    (1)    Be equipped with outlet devices which limit the flow of hot water to a maximum of 0.5 gpm, or
    (2)    Be equipped with devices which limit the outlet temperature to maximum of 110 degrees Fahrenheit, or
    (3)    Be equipped with self-closing valves that limit delivery to a maximum of 0.25 gallons of hot water.
(c)    Piping Insulation. Piping in return circulation systems shall be insulated so that heat loss is limited to a maximum of 17.5 Btu/h per linear foot of pipe. Maximum heat loss shall be determined at a temperature differential equal to the maximum water temperature minus a design ambient temperature not higher than 65 degrees Fahrenheit.
    EXCEPTION. Conformance with Table No. 16-5G for low temperature piping systems shall be deemed as complying with this section.
(d)    Pump Operation. Circulating hot water systems shall be arranged so that the circulating pump can be turned off either automatically or manually when the hot water system is not in operation.
(e)    Performance Efficiency.
    (1)    All automatic electric storage water heaters shall have a standby loss not exceeding four watts per square foot of tank surface area. This method of test of standby loss shall be in accordance with acceptable engineering principles.
    (2)    All gas and oil-fired automatic storage heaters shall have a recovery efficiency, Er, not less than 75 percent and a standby loss percentage, S, not exceeding S = 2.3 + 67/V, where V = rated volume in gallons. The method of determining Er and S shall be in accordance with acceptable engineering principles.
    (3)    Service water heating equipment shall not be dependent on year-round operation of space heating boilers, that is, boilers that have as another function winter space heating.
(f)    Insulation. Unfired hot water storage tanks shall be insulated so that heat loss is limited to a maximum of 13.6 Btu/h per square foot of external tank surface area. For purposes of determining this heat loss, the design ambient temperature shall be not higher than 65 degrees Fahrenheit.
(Sec. 16-7.8, R.O. 1978 (1987 Supp. to 1983 Ed.); Am. Ord. 90-57)

Sec. 16-5.9    Controls.
(a)    Temperature Controls. All hot water supply systems shall be equipped with automatic temperature controls capable of adjustments from the lowest to the highest acceptable temperature settings for the intended use.
(b)    Shut Down. A separate switch shall be provided to terminate the energy supplied to electric hot water supply systems. A separate valve shall be provided to turn off the energy supplied to the main burner of all other types of hot water supply systems.
(Sec. 16-7.9, R.O. 1978 (1987 Supp. to 1983 Ed.); Am. Ord. 90-57)

Sec. 16-5.10    Lighting power limit for buildings.
(a)    General. This section establishes the maximum power limit for interior and exterior illumination systems.
(b)    Exempt Buildings. Buildings housing Group R, Division 3 occupancies, and the dwelling unit portion of buildings housing Group R, Division 1 occupancies are exempt from the requirements of this section.
(c)    Lighting Power Limit. A lighting power limit is the upper limit of the power to be available to provide the lighting needs of a building.
(d)    Separate lighting power limit shall be calculated for the building interior and for the building exterior.
(e)    Calculation Procedure. To establish a lighting power limit, the following procedure shall be used:
    (1)    Interiors.
        (A)    Determine the use categories for the various parts of the building from Table No. 16-5I.
        (B)    Multiply the maximum power limit for each category by the gross floor area included in that category.
        (C)    Add the total watts for each area to arrive at the lighting power limit for the building. Where ballasts are used, include wattage of ballasts.
        (D)    In open-concept spaces in excess of 2,000 square feet, with no defined egress or circulation pattern, 25 percent of the area shall be designated as subparagraph (B) of this paragraph.
    (2)    Exteriors.
        (A)    Category E Lighting (see Table No. 16-5I) -- Multiply the limit given in Table No. 16-5I by the number of lineal feet in the building perimeter. Except for lighting required for security and safety, category E lighting shall be off from two a.m. to 15 minutes before sunset.
        (B)    Other Exterior Lighting -- Multiply the value in category F in Table No. 16-5I by the area to be illuminated.
    (3)    Exception. Lighting for theatrical, television, cleanrooms, spectator sports and like performances shall not be included in the total building limit. Control of this lighting shall have limited access.
(f)    Alternates.
    (1)    The installed lighting power for any area may be increased or decreased from the values of Table No. 16-5I, provided the total interior building lighting power limit calculated in subsection (e) of this section is not exceeded. The task lighting for any area shall not exceed the standards set forth in the 1981 edition of the Illuminating Engineering Society (IES) Handbook.
    (2)    Lighting for retail stores may use five watts per square foot for the first 500 square feet and 2.5 watts per square foot for floor area in excess of 500 square feet.
(g)    Lighting Switching. In all exterior areas, lighting fixtures shall be switched automatically for non-operation when natural light is available.
(h)    Documentation. Lighting power loads shall be presented to the building official in an acceptable format and shall include the total connected lighting wattage per square foot for the entire structure.
(i)    Application to Existing Buildings.
    (1)    General. The provisions of this section shall apply to all existing buildings and structures with a gross floor area in excess of 10,000 square feet.
    (2)    Exempt Buildings and Lighting. The following are exempt from the provisions of this section:
        (A)    Buildings housing Group R, Division 3 occupancies and the dwelling unit portion of buildings housing Group R, Division 1 occupancies.
        (B)    The manufacturing portion of industrial plants.
        (C)    Exterior lighting, provided that subsection (g) of this section shall apply to exterior lighting for existing buildings or portions of existing buildings not exempt under subparagraphs (A) and (B) of this paragraph.
    (3)    Existing Buildings. For the purposes of this section, existing buildings shall be as defined under UBC Section 403.
    (4)    Calculation Procedure. Lighting power limit for existing buildings shall be established following procedure set forth in subsection (e) of this section.
    (5)    Alternates. The alternates set forth in subsection (f) of this section shall also be applicable to existing buildings.
    (6)    Documentation. Lighting power loads shall be presented to the building official in an acceptable format and shall include the total connected lighting wattage per square foot for the portion of a structure under consideration.
(Sec. 16-7.10, R.O. 1978 (1987 Supp. to 1983 Ed.); Am. Ord. 90-57)

Sec. 16-5.11    Energy conservation in electrical distribution systems.
(a)    Power Factor. The power factor of the overall electrical distribution system in a building shall be not less than 90 percent under rated design installed load of the building, either by utilizing equipment design or by the use of power factor corrective devices. The corrective methods shall be based upon an engineering evaluation of each distribution system.
(b)    Lighting Switching. Switching shall be provided for each lighting circuit, or for portions of each circuit so that the partial lighting required for custodial or for effective complementary use with natural lighting may be operated selectively.
(Sec. 16-7.11, R.O. 1978 (1987 Supp. to 1983 Ed.); Am. Ord. 90-57)

Sec. 16-5.12    Violation--Penalty.
    For violation and penalty provisions, see Article 10 of this chapter. (Sec. 16-7.12, R.O. 1978 (1987 Supp. to 1983 Ed.); Am. Ord. 90-57)


Table No. 16-5A
Criteria for Group R Occupancy Buildings Three Stories or Less in Height
 
lement  
Mode   U o  
Walls  
Cooling  
0.47  
Roof/ceiling  
Heating &
Cooling  
0.06  
Roof w/o ceiling*  
 
0.15  
Floors over unheated spaces  
Heating  
0.47  

*Use this when a ceiling air plenum is involved.

Table No. 16-5B
Criteria for Buildings Other Than Group R Occupancy Three Stories or Less in Height
 
Element  
Mode   U o   OTTV  
Walls  
Heating  
0.47    
 
Cooling  
  28.5  
Roof/ceiling  
Heating &
Cooling  
0.06    
Roof w/o ceiling*  
 
0.15    
Floors over unheated spaces  
Heating  
0.47    

*Use this when a ceiling air plenum is involved.

Table No. 16-5C
Minimum EER and COP for Electrically Driven Air-Conditioning System Equipment
 

Standard Rating Capacity  
Air Cooled   Water or Evap. Cooled  
 
EER   COP   EER   COP  
Under 65,000 Btu/hr (19 kilowatts)  
7.8  
2.28   8.8   2.58  
65,000 Btu/hr (19 kilowatts) and over  
8.2  
2.40   9.2   2.69  


Table No. 16-5D
Minimum COP for Heating, Ventilating and Air-Conditioning System Heat Operated Cooling Equipment
 
Heat Source  
Minimum COP  
Direct fired (gas, oil)  
0.48
 
Indirect fired (steam, hot water)  
0.68
 


Table No. 16-5E
Minimum COP for Electrically Driven Air-Conditioning System Components
 
 
Air   Water   Evap.  
Component  
Condensing Means   EER   COP   EER   COP   EER   COP  
Self-contained water chillers  
Centrifugal  
8.0   2.34   13.8   4.04      
 
Positive Displacement  
8.4   2.46   12.0   3.51      
Condenserless water chillers  
Positive Displacement  
9.9   2.90   12.0   3.51      
Condensing units 65,000 Btu/hr (19 kilowatts) and over  
Positive Displacement  
9.5   2.78   12.5   3.66   12.5   3.66  


Table No. 16-5F
Minimum COP for Heat Pumps, Heating Mode
 
Source and Outdoor Temperature, ˚˚Degrees F  
Minimum COP  
Air Source  - 47 dB/43WB  
2.7
 
Air Source  - 17 dB/15WB  
1.8
 
Water Source  - 60 Entering  
3.0
 


Table No. 16-5G
Minimum Pipe Insulation
 


Piping System Types  
Insulation Thickness in Inches for Pipe Sizes  
 
Fluid Temperature Range, Deg.F  

Runouts Up to 2”  

1” and Less  

1 1/4 to 2”  

2 1/2 to 4”  

5” & 6”  

8” & Larger  
Heating Systems
Steam and Hot Water High Pressure/Temp.  

306-450  


1 1/2  



2 1/2  

2 1/2  


3  


3 1/2  


3 ½  

Med. Pressure/Temp.  
251-305  
1 1/2   2   2 1/2   2 ½   3   3  
Low Pressure/Temp.  
201-250  
1   1 1/2   1 ½   2   2   2  
Low Temperature  
120-200  
½   1   1   1 1/2   1 1/2   1 ½  
Steam Condensate
(for Feed Water)  
Any  
1   1   1 1/2   2   2   2  
 
 
           
Cooling Systems
Chilled Water,
Refrigerant or Brine  
40-55

Below 40  

1/2

1  

1/2

1  

3/4

1 1/2  

1

1 1/2  

1

1 1/2  

1

1 1/2  



Table No. 16-5H
Temperature Difference for Sunlit Walls*
 
Wall Construction
Mass per Unit Area - lbs/ft 2  

TD EQ - Deg.F  
 0-25  
44  
26-40  
37  
41-70  
30  
71 and above  
23  

*Temperature difference for shaded areas need be no greater than the average difference between ambient and inside conditions.


Table No. 16-5I
Lighting Limit (Connected Load) for Listed Occupancies
 


Type of Use  
Max. Limit
Per Square Foot
(Watts)  
Interior
Category A:

Classroom, office, automotive, mechanical area, museum, conference room, drafting, clerical, laboratory, retail stores, manufacturing, process, industrial, kitchen, examining room, open library stacks, athletic facility  


3
 
Category B:

Auditorium, place of assembly, waiting area, spectator area, rest room, dining, working corridor in prison and hospital, transportation terminal, closed book stacks, active storage, hospital bedroom, hotel/motel bedroom, enclosed shopping mall concourse  

1
 
Category C:

Corridor, lobby, elevator, stairway, dead storage, bulk manufacturing  

.5
 
Category D:

Indoor parking  

.25
 
Exterior
Category E:

Building perimeter: Wall wash, facade, canopy
 


5 (per linear foot)
 
Category F:

Outdoor parking  

0.05
 



Revised Ordinances